background image

ZGR SCALABLE 60 

– 300 KVA 

 

 

Manual de operaciones 

www.zigor.com 

65 

 

The  rest  of  the  installation  must  also  be  maintained  adequately.  The  maintenance  tasks  to  be  carried  out  shall 
depend  on  the  different  elements  that  make  up  the  installation,  emergency  generator  and  cabling.  The  battery 
requires special attention. 

 

8.1  Battery maintenance  

 

 

Placing  the  batteries  correctly  so  that  all  their  elements  can  be  easily  reached  facilitates  maintenance. 
Maintenance consists of checking the following aspects: 

 

Cleanliness:  The  elements,  their  connections  and  supports  must  be  kept  clean  and  dry.  It  is 
recommended to protect the terminals and metal connections with diluted vaseline. Do not use cleaning 
products containing solvents and/or harmful substances for cleaning elements with plastic containers. 

 

Connections  and  terminals:  Check  the  tightness  of  nuts  on  the  poles  of  elements  as  well  as  the 
tightness of the electrical connection with at regular intervals of approximately 12 months. 

 

Checking voltages: Check the voltages of elements in order to detect any possible anomalies in these. 

There are sealed lead acid maintenance free batteries inside this series standard models. Battery life depends on 
environment  temperature  and  discharge/charge  cycles,  it  will  be  shortened  if  temperature  raised  or  deep 
discharged. Periodical maintenance is required so as to keep battery in good condition. 

1)

 

The most proper working temperature is 15 to 25 ºC. 

2)

 

Avoid small discharging current. 

 for 24 hours. 

3)

 

Charge  battery  for  at  least  12  hours  every  3  months  if  it  is  free  of  operation.  If  the  environment 
temperature is high, charge it once every 2 months. 

4)

 

For extended backup models, check and clean the battery connectors periodically. 

If backup time has become much less than before, or there is battery fault displayed on the LCD, please contact 
distributors to confirm whether the batteries are needed to be replaced or not.

 

 

Do  not  smoke,  light  a  fire  or  generate  sparks  near  batteries  during  recharging  as  there  is  a  risk  of  fire  and/or 
explosion. 

For cleaning, do not use synthetic material clothes or sponges. Keep batteries clean and dry  at all times. Protect 
them against dirt, dust, metal shavings, etc. 

 

 

 

Efficient maintenance lengthens the service life of batteries and ensures that the unit operates correctly.

 

 

WARNING

 

Before  replacing  batteries,  first  please  turn  off  the  UPS  and  break  off  the  mains.  Remove  your  metallic 
adornment such as finger ring, watch and so on. 
When replace batteries, please use the screwdriver with insulating handle. Do not lay the tools or metallic goods 
on the battery. 
Never reverse or short-circuit between the battery anode and cathode. 

Содержание SCALABLE 60 KVA

Страница 1: ...Operation Manual ZGR SCALABLE 60 300 KVA Online Three phase UPS www zigor com...

Страница 2: ......

Страница 3: ...odes 13 Normal mode 13 Battery mode Stored Energy Mode 13 Bypass mode 14 ECO Mode 14 Maintenance mode Manual Bypass 15 3 2 Turn on off UPS 15 Restart procedure 15 Test procedure 16 Maintenance bypass...

Страница 4: ...SNMP card 61 7 TROUBLESHOOTING 62 7 1 Problems and Solution ZGR SCALABLE 60 300 KVA 62 7 2 Recommended spare parts 63 8 MAINTENANCE 64 8 1 Battery maintenance 65 9 TECHNICAL SPECIFICATIONS 66 10 STAND...

Страница 5: ...designed is defined in the documentation The system shall be exposed only to admissible environmental conditions These are defined in the technical details provided for the equipment ZIGOR accepts no...

Страница 6: ...water For the sake of human being safety please well earth the UPS before starting it Do not throw batteries into a fire as they may explode The standard UPS output with internal batteries can be powe...

Страница 7: ...l and reuse of waste from EEE To dispose of this product and ensure its proper management follow the current local environmental legislation and regulations In this way it will contribute to conserve...

Страница 8: ...s label placed at the rear or on one side of the unit Responsibility for the loss or damage of Products shall transfer to the Customer from the moment ZIGOR places these at his disposal in the place...

Страница 9: ...he UPS can solve most of the power supply problems such as blackout over voltage under voltage voltage sudden drop oscillating of decreasing extent high voltage pulse voltage fluctuation surge inrush...

Страница 10: ...view of ZGR SCALABLE 30 60 kVA Fig 2 3 Rear view of ZGR SCALABLE 30 60 kVA Fig 2 4 Front view of ZGR SCALABLE 30 60 kVA redundant power module and bypass module are optional Fig 2 5 Front view of ZGR...

Страница 11: ...GR SCALABLE 90 300 kVA Fig 2 9 Rear view of ZGR SCALABLE 90 300 kVA Fig 2 10 Front view of ZGR SCALABLE 90 270 kVA Redundant power module and bypass module are optional Fig 2 11 Front view of ZGR SCAL...

Страница 12: ...n mains bypass separation 15 Bypass C input copper bar Wiring must be used when mains bypass separation 16 Input neutral copper bar 17 Output neutral copper bar 18 Ground copper bar 19 Battery positiv...

Страница 13: ...rt NC 12V normally close port 2 SWITCH STATUS OUT 0V output breaker auxiliary contact signal port MT 0V maintenance breaker auxiliary contact signal port BP 0V bypass breaker auxiliary contact signal...

Страница 14: ...for software update and history download 4 RS232 port for communication 5 LCD port 6 CAN port BMS port 7 FE Net port reserve 8 RS485 port for communication 9 RS485 port for communication 10 BAT_T bat...

Страница 15: ...ns and supplies DC power to the inverter while floating and boosting charge the battery simultaneously Then the inverter converts the DC power to AC and supplies the load Fig 3 1 Fig 3 1 Normal mode B...

Страница 16: ...load This is to avoid paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15 ms 50 Hz or less than 13 33 ms 6...

Страница 17: ...module_in switch at the on status 4 When AC MAINS input voltage within the range and the rectifiers of the UPS will be started up in 30 up 5 Switch ON output switch If the rectifier of the module doe...

Страница 18: ...RY breaker 4 Switch OFF MAINS breaker 5 Switch OFF BYPASS breaker 6 Switch OFF OUTPUT breaker At this time the bypass source will supply to the load through the MAINTENANCE breaker 3 2 3 2 Switch to n...

Страница 19: ...g 3 6 When battery normal rectifier starts operation 30 s later inverter starts and operates and the green LED will light on Fig 3 6 Cold Start Shut down procedure 1 Press the INVERTER OFF key on the...

Страница 20: ...single mode is changed to parallel mode set the parallel number for each UPS up to 6 units can be parallel set the ID of each cabinet the ID of each unit must be different 5 Switch ON the input switch...

Страница 21: ...control panel areas and elements Click the main block to enter the main data display window click return to return to the previous window click home page to return to the main page Datas menu This men...

Страница 22: ...ttery Fig 4 4 Moreover it can also be entered through by real time data block the status of the switches dry contacts through clicking on the block enter the corresponding data window Fig 4 4 Status m...

Страница 23: ...submenu Click the bypass block to enter the bypass data display window Fig 4 6 Fig 4 6 Status Bypass submenu 4 1 2 3 Output submenu Click the output block to enter the output data display window Fig 4...

Страница 24: ...enter the battery data display window Fig 4 9 y Fig 4 10 Fig 4 9 Status Battery 1 submenu Fig 4 10 Status Battery 2 submenu 4 1 2 5 Status info submenu To access to the status information click the b...

Страница 25: ...o 2 submenu Fig 4 13 Status Status Info 3 submenu 4 1 2 6 Module submenu Click the module block to enter the module data display window Fig 4 14 Fig 4 14 Status Module submenu Alarm menu It allows vie...

Страница 26: ...5 Alarm menu 4 1 3 1 Curr Alarm submenu Click the curr alarm to enter the current alarm display window Fig 4 16 Fig 4 16 Alarm Curr Alarm submenu 4 1 3 2 History submenu Click the history to enter the...

Страница 27: ...the buzzer is on then click the block buzzer will on and the block will change to green Fig 4 19 Fig 4 18 Alarm Buzzer on submenu Fig 4 19 Alarm Buzzer mute submenu Setting menu There are two levels t...

Страница 28: ...gor com 26 4 1 4 1 Basic Setting submenu Click basic setting Fig 4 23 and enter by input the correct password Fig 4 21 and Fig 4 22 The user password is 111111 Fig 4 21 Password window Fig 4 22 Passwo...

Страница 29: ...re login when the setting value is set click left or right block to change the value Fig 4 25 Settings Basic Settings Password submenu Brightness and backlight time submenu Click the block to change...

Страница 30: ...figuration block to save Fig 4 27 o Date Format has 3 formats o Date current date o Time current time Fig 4 27 Settings Basic Settings Date and Time submenu Communication setting submenu Click the tex...

Страница 31: ...ck the text to select other value or input new value and click save configuration block to save Fig 4 30 to Fig 4 46 o Working Mode Seleccione el modo de trabajo del SAI Single Mode modo nico Parallel...

Страница 32: ...gle and short distance Rs485 for multiple and far distance Fig 4 31 Settings Advanced Settings System Setting 2 submenu o Power Walk in this is enable the UPS to control the interval that each module...

Страница 33: ...ue some power module will turn to inverter mode after setting the sleep mode enable Default value is disable Fig 4 33 Settings Advanced Settings System Setting 4 submenu o Paralallel ID Parallel opera...

Страница 34: ...value can be 5 0 5 step is 0 5 default value 0 Fig 4 35 Settings Advanced Settings System Setting 5 submenu o Battery Group Must modify the number to actual configuration The value can be 1 8 default...

Страница 35: ...be 2 30 2 40 V cell and is 2 30 V cell by default o Aver charging Duration boost charge time limit the value can be 1 999min and is 240 by default Fig 4 37 Settings Advanced Settings System Setting 7...

Страница 36: ...Limit When the difference between the bypass voltage and the rated voltage exceeds the lower threshold for the bypass voltage the system determines that the bypass voltage is abnormal and that the byp...

Страница 37: ...urs The default value is Enable o Bypass Switches Limit Cross currents occur during the transfer between bypass mode and normal mode which impacts the system This parameter specifies the number of tra...

Страница 38: ...connection detection The default value is Disable o BYP Switch Enable or disable bypass breaker connection detection The default value is Disable o BATT Ground Fault Enable or disable battery groundi...

Страница 39: ...n set to normally closed or normally opened The default value is normally opened Setting value No ITEM No ITEM 1 URGENT_ALARM 7 BYPASS_SUPPLY 2 MINOR_ALARM 8 BATTERY_SUPPLY 3 MAIN ABNORMAL 9 NO_SUPPLY...

Страница 40: ...4 submenu Maint menu In this menu the History can be downloaded the touch correction adjusted and done a battery self test Fig 4 47 Fig 4 47 Maint menu 4 1 5 1 USB Wizard submenu This submenu provides...

Страница 41: ...SB Wizard Alarm log output submenu Setting log output submenu Fig 4 50 Fig 4 50 Maint USB Wizard Setting log output submenu 4 1 5 2 Battery Self Check submenu It can be selected the check by Timing Da...

Страница 42: ...4 52 Fig 4 52 Maint Battery Self Check Timing daily submenu Timing weekly Modify the check date time and check time 10S default 10min EOD Fig 4 53 Fig 4 53 Maint Autocomprobaci n de la bater a Timing...

Страница 43: ...ter can be started up or switched off INV ON OFF depending on the configuration Fig 4 56 Single OFF Inverter OFF location UPS Single ON Inverter ON location UPS Parallel OFF Inverter OFF all parallel...

Страница 44: ...42 Fig 4 57 Common Battery Test submenu 4 1 6 3 Fault Clear submenu Clear the current fault not for all faults Fig 4 58 Fig 4 58 Common Fault Clear submenu About Menu It shows the software version Mo...

Страница 45: ...econd Fault LED lit 2 003 REC par cable Fault Twice per second Fault LED lit 3 004 REC Over Current Beep continuously Fault LED lit 4 005 REC Power Fault Beep continuously Fault LED lit 5 007 Input SC...

Страница 46: ...mode Fault Beep continuously Fault LED lit 33 06B Fuse Broken Beep continuously Fault LED lit 34 081 Par cable Fault Twice per second Fault LED lit 35 086 ECU Insert Fault Once per 2 seconds Fault LED...

Страница 47: ...conds Alarm LED lit 13 10F Set Data Err Once per 2 seconds Alarm LED lit 14 121 INV Par cable abnormal Once per 2 seconds Alarm LED lit 15 125 INV Overload Once per 2 seconds Alarm LED lit 16 126 INV...

Страница 48: ...nce per second Alarm LED lit 33 164 Once per second Alarm LED lit 34 151 Ecu Set Data Err Once per 2 seconds Alarm LED lit 35 161 BPS Par cable abnormal Once per 2 seconds Alarm LED lit 36 165 Bypass...

Страница 49: ...re can t be higher than 50 If the UPS is dismantled under low temperature it might be in a condensing condition The UPS can t be installed unless the internal and external of the equipment is fully dr...

Страница 50: ...rnal Battery The UPS and its associated batteries are protected against the effect of over current through a DC compatible thermo magnetic circuit breaker or a set of fuses located close to the batter...

Страница 51: ...ditions such as cable layout or ambient temperatures change perform verification in accordance with the IEC 60364 5 52 or local regulations If the rated voltage is 400 V multiply the currents by 0 95...

Страница 52: ...cables no longer than 50 m Power cable connector requirements UPS CABINET KVA CONNECTOR CONNECTION MODE BOLT TYPE BOLT HOLE DIAMETER TORQUE 30 50 45 60 50 100 75 125 120 150 1 2 m Mains input connect...

Страница 53: ...P 250A 3P 400A 3P 135 150 250A 3P 250A 3P 250A 4P 250A 3P 500A 3P 180 200 225 400A 3P 400A 3P 400A 4P 400A 3P 630A 3P 250 270 500A 3P 500A 3P 500A 4P 500A 3P 800A 3P 300 600A 3P 600A 3P 600A 4P 600A 3...

Страница 54: ...ower cable Refer to the table above and pay attention to the diameter of the connection terminal of the cable that should be greater than or equal to that of the connection poles Fig 5 3 Connection of...

Страница 55: ...er can choose the capacity and the numbers of the batteries according to their desire Fig 5 4 Fig 5 4 External battery connections for long run units WARNING If the load equipment is not ready to acce...

Страница 56: ...e module is inserted properly then the indicator will flash 3 Fix the module with screws 1 at the positioning screw holes 4 Switch on the module_ON switch 3 at the left of the module panel then the re...

Страница 57: ...de The basic installation procedure of a parallel system comprising of two or more UPS modules is the same as that of single module system The following sections introduce the installation procedures...

Страница 58: ...module to keep the outputs of two completely independent UPSs synchronized even if they come from two different power supplies LBS system contains LCD set cable connect and STS device 5 8 3 1 LCD set...

Страница 59: ...GR SCALABLE 60 300 KVA Manual de operaciones www zigor com 57 Fig 5 8 LBS cable installation 5 8 3 3 UPS installation The whole systems are showed below Fig 5 9 Fig 5 9 Installation of the whole syste...

Страница 60: ...3 7 CAN_GND Table 5 5 CAN Connection Available functions of CAN Communicate to BMS Communicate to remote LCD Definici n del puerto de comunicaci n RS485 Definition of port Fig 5 11 Fig 5 11 RS485 port...

Страница 61: ...rt Fig 5 12 Fig 5 12 BAT_T port Table 5 7 DEVICE RJ45 UPS RJ45 DESCRIPCTION Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Pin 7 Pin 7 12 Vdc Pin 8 Pin 8 GND Table 5 7 BAT_T Connection Available function...

Страница 62: ...n and UPS REPO port Table 5 8 BUTTON UPS REPO DESCRIPTION Pin 1 Pin 1 EPO NA Pin 2 Pin 2 EPO 12 V Pin 1 Pin 3 EPO NC Pin 2 Pin 4 EPO 12 V Table 5 8 REPO Connection A remote emergency stop switch can b...

Страница 63: ...ts supports the Modem Dial in PPP function to enable the remote control via the internet when the network is unavailable In addition to the features of a standard NetAgent Mini NetAgent II has the opt...

Страница 64: ...LED does not light on and the UPS operates at battery mode The input switch of the Modules are not switched on input cable is not well connected Switch on the input switch Make sure the input cable is...

Страница 65: ...e UPS 14 Cannot Black start Battery switch is not properly closed Battery fuse is not open Or Battery low Close the battery switch Change the fuse Recharge the battery 15 Buzzer beeps continuously and...

Страница 66: ...side panel and the case bottom 6 monthly o Check on the correct ventilation of the location o Cleaning of the equipment s air inlet filters o Removal of foreign bodies both in the air inlet and outle...

Страница 67: ...charge charge cycles it will be shortened if temperature raised or deep discharged Periodical maintenance is required so as to keep battery in good condition 1 The most proper working temperature is 1...

Страница 68: ...k 300k Module 15 kVA 15k Max Number 3 5 4 10 9 CABINET 10 KVA MODULE 30 KVA 50 KVA 100 KVA Capacity UPS cabinet 10 30 kVA 10 30 kW 10 50 kVA 10 50 kW 10 100 kVA 10 100 kW Module 10 kVA 10k Max Number...

Страница 69: ...ns Short circuit overload overtemperature battery low fan fault Transfer time Utility to Battery 0 ms Utility to bypass 0 ms Overload Line Mode 110 overload for 60 min 125 overload for 10 min 150 over...

Страница 70: ...00 KVA model described in this manual comply with the following European regulations I European electromagnetic compatibility directive EMC Standard EN 62040 1 2008 A1 2013 IEC EN 62040 3 2011 II Unin...

Страница 71: ...ating annual referring to the Installation Conditions When the customer not clearly proves the systematic realization of regular maintenance operations described in the Operating Manual Equipment dete...

Страница 72: ...zigor com Consulte nuestra web para contactar con la red de delegaciones comerciales Refer to our website in order to contact the commercial branches network Veuillez consulter notre page web pour con...

Отзывы: