Fig. 4-38 Settings/Advanced Settings/System Setting (8) submenu
o
Cabinet Shared Battery: Tow parallel ups use common batter bank. The value can be set Disable
and enable, disable by default.
o
Generator on prohibit charging: UPS disable charge the battery if set the value to enable when the
generator signal is enable.
o
Single Battery Volt: Set the battery type, 2 V / 4 V / 6 V / 12 V, 12 by default.
Fig. 4-39 Settings/Advanced Settings/System Setting (9) submenu
o
Bypass Volt Prot Lower Limit: When the difference between the bypass voltage and the rated
voltage exceeds the lower threshold for the bypass voltage, the system determines that the bypass
voltage is abnormal and that the bypass is unavailable. The value can be 10%, 15%, 20%, 30%,
45%. The default value is 45%.
o
Bypass Volt Prot Limit: When the difference between the bypass voltage and the rated voltage
exceeds the upper threshold for the bypass voltage, the system determines that the bypass voltage is
not normal and that the bypass is unavailable.
NOTA
When the voltage level is 380 V, the value range is 10%, 15%, 20%, and 25% (default).
When the voltage level is 400 V, the value range is 10%, 15%, and 20% (default).
When the voltage level is 415 V, the value range is 10% and 15% (default).