36 V00 Installation and operating instructions
5.5.4 Connecting the PV array
Procedure:
1.
Ensure that the AC circuit breaker is switched off and ensure that it cannot be
accidentally reconnected.
2.
Ensure that the DC switch is switched off and ensure that it cannot be
accidentally reconnected.
3.
Ensure that there is no ground fault in the PV array.
4.
Check whether the DC connector has the correct polarity.
If the DC connector is equipped with a DC cable having the wrong polarity, the DC
connector must be re-connected in accordance with the right polarity.
5.
Ensure that the open-circuit voltage of the PV array does not exceed the
maximum DC input voltage of the inverter.
6.
Connect the assembled DC connectors to the inverter until they audibly snap into
place.
7.
Ensure that all DC connectors are securely in place.
The inverter can be destroyed by overvoltage!
If the voltage of the PV module exceeds the maximum DC input
voltage of the inverter, it can be destroyed due to overvoltage. All
warranty claims become void.
• Do not connect strings with an open-circuit voltage greater than the
maximum DC input voltage of the inverter.
• Check the design of the PV system.