16 V00 Installation and operating instructions
Risk of injury when lifting the inverter, or if it is dropped!
When mounting, at least two persons are needed, take into account that
the inverter weighs approximately 58kg.
4.3 Mounting the inverter with the wall bracket
Mounting procedure:
1.
Use the wall bracket as a drilling template and mark the positions of the drill holes
on the wall, drill 6 holes as required using a drill with Ø10 mm bit. The holes must
be
approximately
70 mm deep. Keep the drill perpendicularto the wall, and hold
the drill steady to avoid tilted holes.
2.
Insert six wall plugs into the holes in the wall with a rubber hammer and fix the
wall bracket to the wall by tightening six hexagon screws, using a socket wrench
•Before inserting the wall plugs, measure the depth and distance of the
holes.
•If the measured values do not meet the hole requirements, redrill the
holes.