32 V00 Installation and operating instructions
5.5.2 Assembling the DC connectors
Assemble the DC connectors as described below. Observe the correct polarity. The DC
connectors are marked with the symbols "+" and " − ".
Cable requirements
:
The cable must be of type PV1-F, UL-ZKLA or USE2 and comply with the following
properties:
External diameter: 5 mm to 8 mm
Conductor cross-section: 2.5 mm² to 6 mm²
Number of copper conductors: at least 7
Nominal voltage: at least 1000V
Proceed as the follows:
1.
Strip the cable insulation as shown in the picture below.
2.
Insert the stripped cable all the way into the DC connector.
Danger to life due to high voltages on DC conductors!
When exposed to sunlight, the PV array generates dangerous DC
voltage which is present in the DC conductors. Touching the DC
conductors can lead to lethal electric shocks.
•
Cover the PV modules.
•
Do not touch the DC conductors.