4 Mounting
4.1 Ambient conditions
1.
The mounting location must be inaccessible to children.
2.
The mounting location should be dry, freely and safely accessible at all times
without the need for any auxiliary equipment.
3.
Mount the inverter in areas where it cannot be touched inadvertently.
4.
The mounting method and location must be suitable for the inverter's weight and
dimensions.
5.
The ambient temperature should be below 40°C to ensure optimal operation.
6.
In living areas, do not mount the unit on plasterboard walls or similar to avoid
audible vibrations. The inverter can make noises when in use which may be
perceived as a nuisance in a living area.
7.
Observe the minimum clearances to walls, other inverters, or objects as shown
in the diagram in order to ensure sufficient heat dissipation and sufficient space
for maintaining the inverter.
clearances for one inverter
Direction
Min. clearance
for multiple
inverters
Min. clearance
for a single
inverter
above
200mm
200mm
below
500mm
500mm
sides
600mm
600mm
spacing
1000mm