9.2 Display messages
Along with the various operating states, various messages may be shown on the
display, as follows.
State
Error
code
Description
Causes
Initializat-
ion
Waiting
Initial PV voltage is between minimum DC
input voltage and the start-up DC input
voltage of the inverter.
Checking
The inverter is checking the feed-in
conditions after the start-up PV voltage
exceeds the initial DC input voltage of the
inverter and that both the grid voltage
and frequency are normal .
Reconnect
The inverter is checking feed-in
conditions after the last fault has been
solved.
Normal
Normal
The inverter is feeding energy into grid
normally.
fault
1
SCI Fault
Communication between the master and
slave CPU has failed.
2
EEPROM R/W
Fault
Reading or writing of EEPROM has failed.
3
Rly-Check Fault Output relay has failed.
4
DC INJ. High
Output DC feed-in exceeds the permitted
upper limit.
6
High DC Bus
The voltage of DC bus exceeds the
permitted upper limit.
8
AC HCT Fault
Output current is abnormal
9
GFCI Fault
Ground fault detection circuit is abnormal
10
Device Fault
Unknown Error
33
Fac Fault
The grid frequency is outside the
permitted range.