22
Installation and Operating Instructions
V02
The maximum cable lengths relative to the conductor cross-section as follows:
Conductor
cross-section
Maximum cable length
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
2.5 mm²
46m
37 m
28 m
17 m
4 mm²
74 m
59 m
44 m
27 m
6 mm²
110 m
89 m
67 m
40 m
The required conductor cross-section depends on the inverter rating, ambient
temperature, routing method, cable type, cable losses, applicable installation
requirements of the country of installation, etc.
5.4.2 Grid connection
Damage to the seal of the cover in sub-zero conditions
• If you open the cover in sub-zero condition, the sealing of the cover
can be damaged. This can lead moisture entering the inverter.
• Do not open the inverter at ambient temperatures lower than -5
℃
.
• If a layer of ice has formed on the seal of the cover in sub-zero
comditions, remove it prior to opening the inverter( e.g. by melting the
ice with warm air ). Observe the applicable safety regulation.
Risk of injury due to electric shock and fire caused by high leakage
current
• The inverter must be reliably grounded in order to protect property
and personal safety.
Содержание Zeverlution 1500S
Страница 1: ......