20
Installation and operating instructions
5.4 AC Connection
• Before making the electrical connection, ensure that the miniature circuit-breaker is
switched off and cannot be reactivated.
5.4.1 Conditions for the AC connection
Cable Requirements
The grid connection is made using 5 conductors (L1, L2, L3, N, and PE). We recommend
the following requirements for stranded copper wire.
Object Description
Value
A
External diameter
13 … 17.5 mm
B
Conductor cross-section area
6.0 … 10.0 mm
2
C
Stripping length of the insulated wires
Approx. 9 mm
D
Stripping length of the AC cable’s outer sheath
Approx. 72 mm
The PE insulated conductor must be 2 mm longer than the L and N conductors.
Larger cross-sections should be used for longer leads.
DANGER!
Danger to life due to high voltages in the inverter!