PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE  

 

Approved Document No: GLT.MAN-112 

 

 

Issue: 2.3      Author: NRPJ         Date: 25/5/2017 

 

 

 

8-24 ZONE CONVENTIONAL FIRE ALARM PANEL 

 
 
 

 

 

USER MANUAL & MAINTENANCE 

GUIDE 

 

Содержание Premier M plus

Страница 1: ...PREMIER M PLUS USER MANUAL MAINTENANCE GUIDE Approved Document No GLT MAN 112 Issue 2 3 Author NRPJ Date 25 5 2017 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE...

Страница 2: ...ire extinguishers if suitably trained or call the fire brigade IF IN DOUBT CALL THE FIRE BRIGADE To reset the panel press the reset button If the panel goes back into alarm silence the sounders and ca...

Страница 3: ...LARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL...

Страница 4: ...de called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point The system is split into Zones each covering...

Страница 5: ...operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the PREMIER M PLUS Range of Fire Alarm Panels we recommend the follow...

Страница 6: ...ch may have been programmed into the Panel by pressing the Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid una...

Страница 7: ...ONLY STEADY RED A manual evacuation has occurred The sounders will be active COMMON FIRE ZONE FIRE F A R E ACTIVE STEADY RED STEADY RED STEADY RED A fire has occurred in the zone indicated The sounde...

Страница 8: ...ilenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red...

Страница 9: ...a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel...

Страница 10: ...lt zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear Short Circuit Fault If...

Страница 11: ...he panel On power up the panel looks for a signal from a repeater If it does not see one it assumes there is no repeater connected If the panel sees a repeater but then looses its signal it will show...

Страница 12: ...ash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then...

Страница 13: ...the SOUNDER DELAY LED will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To overrid...

Страница 14: ...te 25 5 2017 User Manual Modification History Do Not Print this Page when creating PDF Of the manual ISSUE DATE CHANGES 2 1 10 11 2010 Version Before addition of modification History 2 2 23 7 2012 Dra...

Отзывы: