Extinguishing Panel - INSTRUCTION MANUAL
Approved Document No: GLT.MAN-124
PAGE 6
Issue : 1 Author: NRPJ Date: 15/11/2007
The Premier EX8 has the following LED indicators:-
LED
COLOUR
FUNCTION / MEANING
POWER
GREEN
The panel is supplied with power, either battery, mains or both
COMMON FIRE
RED
There is an alarm on the system. Check which zone caused the alarm
COMMON FAULT
YELLOW
There is a fault on the system. Another LED(s) will be lit to indicate the specific fault
BATTERY FAULT
YELLOW
There is a problem with the batteries. Rectify or replace.
CHARGER FAULT
YELLOW
The panel is not charging the batteries (usually mains fail or low mains)
LOW BATTERY
YELLOW
The batteries are below their final voltage & should be replaced
EARTH FAULT
YELLOW
Problem in system wiring. At least one cable is shorting to earth.
EXT.FAN DISABLE
YELLOW
The external equipment relay has been disabled
SYSTEM FAULT
YELLOW
The CPU has crashed, (Or CPU reset has been pressed & held)
REMOTE FAULT
YELLOW
The panel has received a fault input from external equipment
REPEATER FAULT
YELLOW
The panel has lost communication with the repeater panel
GEN S/C FAULT
YELLOW
Indicated that a line fault is caused by a short circuit
EXTINGUISHANT RELEASED
RED
The bottle output has been activated & the gas released
RELEASE IMMINENT
RED
The panel has started the release timer and will activate bottle imminently
HOLD/ABORT
GREEN
An emergency hold OR emergency abort input has been activated.
MANUAL RELEASE
RED
A manual release call point has been activated
1
ST
STAGE ALARM
RED
One of the crossed zones is in alarm
2
ND
STAGE ALARM
RED
Both of the crossed zones are in alarm
LOW PRESSURE
YELLOW
A drop in bottle pressure has been detected
FLOODING ZONE FAULT
YELLOW
There is a fault relating to the flooding zone1
MANUAL MODE
YELLOW
The panel is in manual only mode (ie will not be triggered by detectors)
AUTOMATIC MODE
GREEN
The panel is in automatic or manual mode
GENERAL DISABLEMENT
YELLOW
Lights when any section of the system is disabled
GENERAL TEST
YELLOW
Lights when any section of the panel is in test mode
CONTROLS ACTIVE
YELLOW
Lights when controls enabled keyswitch is on
ZONE 1-6 FIRE
RED
Lights when one of the detection zones is in alarm
ZONE 1-6 FAULT
YELLOW
Lights when one of the detection zones has a fault
ZONE 1-6 TEST
YELLOW
Lights when one of the detection zones is in test mode
ZONE 1-6 DISABLED
YELLOW
Lights when one of the detection zones is in disablement mode
1
ST
STAGE SNDR ACTIVE
RED
Lights when the first stage sounder is on
1
ST
STAGE SNDR FAULT
YELLOW
Lights when the first stage sounder has a wiring fault
1
ST
STAGE SNDR TEST
YELLOW
Lights when the first stage sounder is in test mode
1
ST
STAGE SNDR DISABLED
YELLOW
Lights when the first stage sounder is disabled
2
ND
STAGE SNDR ACTIVE
RED
Lights when the second stage sounder is on
2
ND
STAGE SNDR FAULT
YELLOW
Lights when the second stage sounder has a wiring fault
2
ND
STAGE SNDR TEST
YELLOW
Lights when the second stage sounder is in test mode
2
ND
STAGE SNDR DISABLED
YELLOW
Lights when the second stage sounder is disabled
BOTTLE OUTPUT ACTIVE
RED
Lights when the bottle output is on
BOTTLE OUTPUT FAULT
YELLOW
Lights when the bottle output has a wiring fault
BOTTLE OUTPUT TEST
YELLOW
Lights when the bottle output is in test mode
BOTTLE OUTPUT DISABLED
YELLOW
Lights when the bottle output is disabled
1
ST
STAGE RELAY ACTIVE
RED
Lights when the first stage relay is on
1
ST
STAGE RELAY TEST
YELLOW
Lights when the first stage relay is in test mode
1
ST
STAGE RELAY DISABLED
YELLOW
Lights when the first stage relay is disabled
2
ND
STAGE RELAY ACTIVE
RED
Lights when the second stage relay is on
2
ND
STAGE RELAY TEST
YELLOW
Lights when the second stage relay is in test mode
2
ND
STAGE RELAY DISABLED
YELLOW
Lights when the second stage relay is disabled
MAN.L RELEASE INPUT ACTIVE
RED
A manual release call point connected to the remote input has been activated
MAN. RELEASE INPUT FAULT
YELLOW
Fault in wiring to Manual release call point
MAN. RELEASE INPUT DISABLED
YELLOW
Manual release remote input has been disabled
GAS FIRED INPUT ACTIVE
RED
The panel has received a signal from the cylinder to say the gas has been released.
GAS FIRED INPUT FAULT
YELLOW
There is a wiring fault to the bottle`s sensor
GAS FIRED INPUT DISABLED
YELLOW
The Gas fired remote input has been disabled.
EMERG. HOLD INPUT ACTIVE
RED
The emergency hold input has been activated
EMERG. HOLD INPUT FAULT
YELLOW
Fault in wiring to Emergency hold switch
EMERG. HOLD INPUT DISABLED
YELLOW
The emergency hold input has been disabled
EMERG. ABORT INPUT ACTIVE
RED
The emergency abort input has been activated
EMERG. ABORT INPUT FAULT
YELLOW
Fault in wiring to Emergency abort switch
EMERG. ABORT INPUT DISABLED
YELLOW
The emergency abort input has been disabled
AUTO/MANUAL INPUT ACTIVE
RED
The panel has been set to manual mode by a remote input
AUTO/MANUAL INPUT FAULT
YELLOW
Fault in wiring to Auto / Manual switch
AUTO/MANUAL INPUT DISABLED
YELLOW
The Auto / Manual remote input has been disabled.
PRESS. SWITCH INPUT ACTIVE
RED
The bottle`s pressure switch output has been activated
PRESS. SWITCH INPUT FAULT
YELLOW
Fault in wiring to bottle`s pressure switch
PRESS. SWITCH INPUT DISABLED
YELLOW
The pressure switch input has been disabled
BOTTLE SCALES INPUT ACTIVE
RED
The bottle`s scales switch has been activated
BOTTLE SCALES INPUT FAULT
YELLOW
Fault in wiring to bottle`s scales switch
BOTTLE SCALES INPUT DISABLED
YELLOW
The bottle`s scales iinput has been disabled
ACCESS LEVEL 3
YELLOW
Access level 3 selected
GAS RELEASE COUNTER
YELLOW
Gas release counter is being displayed on 3 digit display
RELEASE DURATION TIME
YELLOW
Release duration time is being displayed on 3 digit display
RESET INHIBIT TIME
YELLOW
Reset inhibit time is being displayed on 3 digit display