Extinguishing Panel - INSTRUCTION MANUAL
Approved Document No: GLT.MAN-124
PAGE 4
Issue : 1 Author: NRPJ Date: 15/11/2007
Introduction
The Premier EX 8 is a combined 2 zone , 1 area extinguishing panel, and 4 zone
conventional fire alarm panel.
The Extinguishing section is designed to BSEN12094-1:2003.
The fire alarm section is designed to EN54-2 & 4.
This design allows the same panel to protect an extinguishing area, and also monitor
the rest of the site for a fire.
The panel has an integral Manual Release call point fitted to the front of the panel.
The panel has monitored inputs for field connections, such as manual release,
emergency hold, etc.
The panel has relay outputs for first & second stage alarms, fault & gas fired.
The panel has remote inputs for Stop/Start Sounders, Silence & Reset, to allow the
panel to be controlled remotely.
The panel has Open collector repeat outputs for most panel status indications (eg 1
st
stage alarm, 2
nd
stage alarm, Automatic mode, Manual mode etc)
The panel has a connection for a serial repeater unit (4 wire)