INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 27
12.8.5 CONFIGURING ALARM OUTPUT RESOUND OPERATION
Some installations require the sounders to operate in a certain way to new alarms if the
sirens have been silenced. To Access the settings, go to
Engineer menu 1 / Config alarms / Resound
. The panel shows the following screen.
Press Prev/Next to scroll between the options. The options are:-
•
Resound for any new alarm
•
Resound for a new zone in alarm
•
Only activate for first alarm (ie don`t resound)
Scroll to required option and press enter to save.
12.9 Setting the LCD language
From Engineer menu 2, Select Misc (option 6)
Then from the Misc Settings menu, select option 1 (Language)
Pressing Prev / Next will scroll through the available languages.
The panel will have one of 2 language banks:-
English
Spanish
Portuguese
French
Italian
OR
English
Hungarian
Serbian
Lithuanian
Other languages are available on request.
12.10 Software Versions
From Engineer menu 2, select Misc (option 6)
Then from the Misc Settings menu, select option 2 (Version)
The panel will display the software versions in its two Microcontrollers,
one for the main functions and one for the Loop Driver. This information may
be useful for technical support in the Event of any problems occurring
with the Control Panel.
(Note that the revision number is an internal reference number. It does not mean that there have been 8600+
software revisions)
Engineer Menu 2
4: Alarm Verify
5: Config Alarms
6: Misc
Misc Settings
1: Language
2: Version
3: Topology 6: Reset
Set Language
English
Press ENTER to Save
Misc Settings
1: Language
2: Version
3: Topology 6: Reset
GLT Exports Ltd
Infinity ID2/8 Zone
Panel : 1.a. 8687
Loop : 0.k. 8680
Alarm Resound
Any New Alarm
Enter to Confirm