Receiver sensitivity (RX Sense) will start by rising to 100% and then the output power
(IRpower) will rise to 100%. More power will be output than is necessary to cover the
distance and these levels will then be reduced once the auto align process takes place.
Pre-Align Complete will now be indicated
9.
Press enter to accept Pre-Alignment
and confirm these settings by pressing the
right key and enter
into Manual Alignment
.
The ZetaBeam is looking for the far wall of the building and in some shorter distances applications will
stop raising the IR power when its sufficient for the distance.
In these cases you can press Enter to
accept the Pre-Alignment then right key and enter into Manual Alignment.
CAUTION:
If you have not allowed the 50cm radius and the ZetaBeam encounters an obstruction this will
also stop raising the IR power and halt the Pre Alignment as the beam will assume it has found the far
wall. You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam.
You can identify that the beam is obstructed by the right hand figure (Air Quality) has risen and may
fluctuate between 5% - 10%.
Obstructions near the head will disturb the pre-alignment process and care should be taken to ensure no
solid objects are close to the beam path.
Ensure 1 m of clear space along the path of the beam and 500mm from the
edges of the relector.
If the wall you are placing the reflector/s on is shiny or glass then the reflectors
should be be placed on a 1 meter piece of non-reflective material like MDF to
ensure correct operation.
Obstacle
Roofline
Target wall
Sufficient power
f
or distance
Reflections from near
b
y objects will
limit the output power and prevent
a
bility of the beam to cover the
required distance
Pre-Align - Complete
Press
(right)
Manual Alignment
enter
right
Manual AQ 0%
X+0.00
0
Y+0.00
0
10.0%
100% 0% P
X+0.000 Y+0.000
Press (right)
to confirm
Manual Alignment
enter
right
Manual AQ 0%
X+0.00
0
Y+0.00
0
enter