3 Screen and menu systems

Home screen

This is the screen you would normally see when the beam is commissioned.

Other screens you may see are:

Air Quality 100%

Status - NORMAL

The air quality level has fallen below the fire threshold setting.

If alarm is set to latching and you need to reset from fire press 

enter

 to 

see this screen:

and press 

enter

 

again to reset and return to the 

normal screen.

This can also be reset by dropping the power to the beam for 5 seconds. If set 
to auto reset it will reset to normal automatically.

The beam path has been fully blocked within 1 second (used when 
fault testing in commissioning.

No communication with the controller. This could be that the flying 
lead is not connected, or that the head is not connected to the 
controller, this can be checked by reading the resistance across the 
black and grey terminals, if connected it should read 110ohms if not 
connected at one end this will read 220ohms.

This screen will appear when the beam is performing a self 
alignment, normally because of building movement.

This is due to the compensation for dirt build up reaching its 
maximum - 

FAULT

 or 

FIRE LED 

may be flashing.

How to use the menu system

Press 

enter

 

to go into the menu system, then press 

down

 

to go through the main menu options:

enter

 

here to change languages.

enter

 

here to commission ZetaBeam.

enter

 

here to make all changes and adjustments to the beam.

enter

 

here as part of your routine maintenance.

enter

 

here to access power and temperature headings.

FIRE

FAULT

ALIGN

DIRT
COMP

ERROR

Air Quality 29% 

Status - FIRE

Alarm Reset

English

Commission

Mode Change

Beam Maintenance

Diagnostics

enter

enter

enter

enter

enter

enter

enter

enter

down

Air Quality 0%

Status - FAULT

Air Quality 89%

Status - ALIGN

Status - Dirt Comp

Air Quality XX

Status - ERROR

Содержание Zeta Beam

Страница 1: ...The ZetaBeam Protection System Xtra User Guide 0150 01...

Страница 2: ...rt range mask supplied on the single reflector 7 to 70 metres the standard ZetaBeam The standard ZetaBeam comes boxed with the head unit low level controller key and quick start installation guide thi...

Страница 3: ...t along its entire axis Note Careful design consideration should be made when positioning beams and reflectors in environments that can be susceptible to condensation i e warehouses near to water that...

Страница 4: ...ction is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connec...

Страница 5: ...To re panel To controller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44...

Страница 6: ...ne beam To controller Beams 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Ph...

Страница 7: ...raw it may be necessary to use normal mode to prevent excessive current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is...

Страница 8: ...ill assume it has found the far wall You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam You can identify that the beam is obstructed by the right hand fig...

Страница 9: ...the angle of the beam Y until you receive an AQ of over 100 Re ector is lower than the beam head use Y to bring the beam onto the re ector Beam head Re ector y x x y Manual AQ 125 X 0 000 Y 0 000 Manu...

Страница 10: ...and would normally be below 0 90 If this is not the case you may need to start the Manual Alignment process again to return both the zetabeam axis to 0 00 and identify and remove the obstruction Air Q...

Страница 11: ...ding the resistance across the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a sel...

Страница 12: ...o return signal is received the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually...

Страница 13: ...uto reset The beam is factory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right a...

Страница 14: ...before it returns to normal This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and...

Страница 15: ...g needs to be maintained in the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go...

Страница 16: ...s Electrical Specifications Supply Voltage 12 to 30 VDC Supply Current 3 5mA constant current in all operational states Constant Current 17mA constant current in fast commissioning Environmental Speci...