background image

3. Here we can make changes to how the beam behaves. Press 

enter

to go into 

mode change

 and the sub menus.

Threshold

. Use the 

right

 and 

left

 keys to increase or decrease the beams sensitivity. 

It is factory set at 35% (meaning the received signal has to drop by 35% to trigger 

the fire relay. This sensitivity can be adjusted between 

25% (sensitive) 

and 

50% (less 

sensitive) 

(press 

enter

 to return to 

mode change

 or 

down

 to go to 

time to fire

).

Time to fire

. Here we can adjust how long the beam has to be in fire before the fire 

relay is triggered. This is factory set at 10s, you may want to increase this if there is 

something that may momentarily obscure the beam path (birds / forklift truck) this 

can be adjusted between 

2

 and 

30 seconds 

by using the 

right

 and 

left

 keys (press 

enter

 to return to 

mode change

 or 

down

 to go to 

time to fault

).

Time to fault.

 Here we can adjust the time to fault between 

and 

60 seconds

 

(factory set at 

10 seconds

). For a beam to go into fault the beam path must be totally 

blocked within 

ONE

 second. By using the 

right

 and 

left

 keys (press 

enter

 to return to 

mode

 

change

 or 

down

 to go to 

auto reset

).

Auto reset

. The beam is factory set to 

auto reset 

when the received signal raises 

above the fire threshold 

hysteresis

. This can be set to latching if your system requires 

this. Change by using the 

right

 and 

left

 keys (press 

enter

 to return to 

mode change

 or 

down

 to go to 

align on / off

).

Align on / off

. You may want to turn the auto alignment function off, for example, 

in an environment that often gets filled with welding smoke, the auto align function 

kicks in when the received signal drops below 

90%

, the point that the beam 

automatically checks for building movement. The beam will try to align through the 

smoke which could be a problem if it is unable to see the edges of the reflector. Use 

the 

right

 and 

left

 keys to turn off and on. When turning this function off extra care 

should be taken to ensure that the beam head is on a sturdy fixing ie., brick wall or 

major structural steel. 

Auto alignment

 will still function in 

commissioning

 (press 

enter

 

to return to 

mode

 

change

 or 

down

 to go to 

align time

).

Align time

. This is factory set to 4hrs, you can adjust this, by using the 

right

 and 

left

 

keys, between 

0

 to 

12 hours

 depending on your environment (press 

enter

 to return to 

mode change 

or 

down

 to go to 

green flashing light

).

enter

Mode Change

Threshold

Time to fire

Time to fault

Auto reset

Align On/Off

Align Time

enter

Содержание Zeta Beam

Страница 1: ...The ZetaBeam Protection System Xtra User Guide 0150 01...

Страница 2: ...rt range mask supplied on the single reflector 7 to 70 metres the standard ZetaBeam The standard ZetaBeam comes boxed with the head unit low level controller key and quick start installation guide thi...

Страница 3: ...t along its entire axis Note Careful design consideration should be made when positioning beams and reflectors in environments that can be susceptible to condensation i e warehouses near to water that...

Страница 4: ...ction is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connec...

Страница 5: ...To re panel To controller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44...

Страница 6: ...ne beam To controller Beams 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Ph...

Страница 7: ...raw it may be necessary to use normal mode to prevent excessive current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is...

Страница 8: ...ill assume it has found the far wall You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam You can identify that the beam is obstructed by the right hand fig...

Страница 9: ...the angle of the beam Y until you receive an AQ of over 100 Re ector is lower than the beam head use Y to bring the beam onto the re ector Beam head Re ector y x x y Manual AQ 125 X 0 000 Y 0 000 Manu...

Страница 10: ...and would normally be below 0 90 If this is not the case you may need to start the Manual Alignment process again to return both the zetabeam axis to 0 00 and identify and remove the obstruction Air Q...

Страница 11: ...ding the resistance across the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a sel...

Страница 12: ...o return signal is received the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually...

Страница 13: ...uto reset The beam is factory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right a...

Страница 14: ...before it returns to normal This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and...

Страница 15: ...g needs to be maintained in the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go...

Страница 16: ...s Electrical Specifications Supply Voltage 12 to 30 VDC Supply Current 3 5mA constant current in all operational states Constant Current 17mA constant current in fast commissioning Environmental Speci...

Отзывы: