DISABLEMENT 

 

On the Simplicity, there are 2 disablement options. A whole zone of detectors can be disabled, or an individual 
point can be disabled. Both types of disablement can be used at the same time if required. 

 

 ZONE DISABLEMENT 

 
To aid commissioning and assist routine maintenance checks, any of the zones or the loop sounders can be 
disabled. 
 
When a zone is disabled, the panel will not respond to any fault or fire signals it receives from DETECTORS from 
that zone. Call points will remain operational.  

This might be used if the system requires routine maintenance, and the customer needs the system to continue 
running, but doesn’t want spurious false alarms.  

The panel will respond in the usual manner to any events in any non-disabled zones. 

 
The Simplicity also allows the loop sounders to be disabled. If they are disabled, the panel will not start any 
sounders in an alarm condition. 
 

TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED 

 
Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one zone at a time. 
 
1.

 

Press ENTER button, then enter access code 123. 

 
2.

 

Press GENERAL DISABLEMENT button and the screen will  
show: ZONE DISABLEMENT ZONE 1. The panel is now in  
SELECT DISABLEMENT MODE. 

 
3.

 

Press NEXT (or PREV) until the required zone or loop sounders is  
DISPLAYED. Press ENTER button to disable this section.  The screen  
will now show that the zone is disabled, and the GENERAL  
DISABLEMENT LED will be on. This section is now disabled. 
 

(NOTE: Call points in this zone will still be active. To disable the  

call points as well, disable them individually as points – see next section) 

 
4.

 

If more than one zone (or sounder) needs to be disabled, then press  
NEXT (or PREV) again until the required zone (or sounder) is selected. 

 
5.

 

If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on another 
part of the system), either press GENERAL DISABLEMENT button, or press cancel. 

 
6.

 

Once all the maintenance work has been done, the zones need to be enabled again. If the panel is still in 
SELECT DISABLEMENT MODE, jump to paragraph 7, otherwise, press GENERAL DISABLEMENT 
button. (if access is not on, you will have to enter the code 123, then press General disablement again. The 
panel is now in SELECT DISABLEMENT MODE 

 
7.

 

Press the NEXT (or PREV) button until the disabled zone is displayed on the screen. Press ENTER  button 
to de-select disablement. Scroll to any other disabled zone and enable in the same way. When all zones are 
enabled again, the GENERAL DISABLEMENT LED will turn off. Either press GENERAL 
DISABLEMENT button, or press cancel to return the system to normal. (NOTE: This will also enable any 
points individually disabled in that zone) 

 

  Zone Disablement 
      Zone  1

        

 

Enabled 

Single Devices:  0 

  Zone Disablement 

      Zone  3

        

 

Disabled 

Single Devices:  0 

Содержание SIMPLICITY MICRO

Страница 1: ...Instruction Manual ADDRESSABLE FIRE ALARM PANEL ci mpli y t Micro...

Страница 2: ...SETTING TIME AND DATE 11 SETTING A CUSTOM BANNER 11 VIEWING DEVICE STATUS 12 LOCATE OR VERIFY A DEVICE 13 USING THE EVENT LOG 13 CHECKING SOFTWARE VERSION 14 DISABLEMENT 15 ZONE DISABLEMENT 15 TO PRO...

Страница 3: ...an alarm and each detector can be labelled with a 20 character description to further improve user friendliness An exact location is much more useful for locating the cause of an alarm rather than ju...

Страница 4: ...d be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the Fire Panel MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED Connecting the batteries The Simplicity M...

Страница 5: ...sounders and several other interface units can be connected to these loops A MAXIMUM OF 32 DEVICES CAN BE CONNECTED TO THE LOOP I O H I O I O O H I I I O O O O H O SIDE A VE SIDE A VE SIDE B VE SIDE B...

Страница 6: ...ON ON ON 29 OFF ON OFF OFF OFF ON ON 13 OFF ON OFF OFF ON ON ON 30 ON OFF OFF OFF OFF ON ON 14 ON OFF OFF OFF ON ON ON 31 OFF OFF OFF OFF OFF ON ON 15 OFF OFF OFF OFF ON ON ON 32 ON ON ON ON ON OFF ON...

Страница 7: ...e r F la s h e r w ith S h o rt C irc u it L o o p Is o la to r S o un d e r to ecure S e n Micro Heat Detector Sm oke Detector Addressable Sounder Flasher Base S A d d r e s s MODEL SM ASFIB SM ASB S...

Страница 8: ...ly giving a fault or an alarm it may be desirable to disable that zone until the system is serviced To disable a zone 1 Press General Disablement button 2 Enter Access Code if prompted 3 4 Press ENTER...

Страница 9: ...EXT Used to display the Next message or next event in log in LCD PREV Used to display the Previous message or Previous event in log in LCD GENERAL TEST Used to initiate test mode GENERAL DISABLEMENT U...

Страница 10: ...re the loop The panel displays configuration in progress Please wait It will return to Configuration Menu 2 when completed 7 Press PREVIOUS button followed by button 1 to view the loop contents It lis...

Страница 11: ...cancel again to exit the menu and to return to normal The panel is now configured and ready for operation SETTING TIME AND DATE To set the time date enter Configuration Menu 2 and select Configure Sy...

Страница 12: ...escription of the fault will appear here It will show one of the following messages FAULT MEANING Changed The device had been changed with one of a different type since last configuration The message...

Страница 13: ...nd the Zone loop and address if appropriate Next Previous buttons will cycle through the list System The Simplicity also records other non critical items such as keyswitch turned on etc These can be u...

Страница 14: ...e version from the LCD screen From Configuration menu 2 select configure system The System Menu Will Be displayed Press 2 Version Info and the panel will display the software in its two Microcontrolle...

Страница 15: ...now in SELECT DISABLEMENT MODE 3 Press NEXT or PREV until the required zone or loop sounders is DISPLAYED Press ENTER button to disable this section The screen will now show that the zone is disabled...

Страница 16: ...rom the disablement screen Press disable then press NEXT to scroll through all the zones sounders If there are no disablements the screen will show If the whole zone is disabled the screen will show I...

Страница 17: ...ter the cause of the alarm has been checked and the panel reset test mode will have to be selected again to resume testing TO PROGRAMME ZONE IN TEST MODE NOTE Only one zone can be programmed in test a...

Страница 18: ...extinguisher 5 If a larger fire is found leave the building immediately and contact the fire brigade 6 If no fire is found make a note of the detector that signalled fire and look for anything nearby...

Страница 19: ...uit wiring fault Detector removed Double address installation fault Most of these faults will need to be checked by an engineer but the system can be checked for a removed detector by the responsible...

Страница 20: ...ears this verifies the fault Break the earth screen aprox half way along the loop at a detector Connect loop side A screen to earth If no fault this half of the cable is clear Disconnect earth again C...

Страница 21: ...panel will also report a break if there are 2 loop short circuit isolators active Look for isolators or sounder flasher isolators with Yellow isolating LEDs on Device faults If the panel is showing a...

Страница 22: ...panel sees it at a different address If the device is giving no further details of the fault then the device in fault is communicating OK with the control Panel but is reporting a fault that it has de...

Страница 23: ...d battery backup required we use the equation Battery Size Standby time in Amp Hours 1 25 x TALM x IALM TSBY x ISBY Where TALM Maximum time in hours required for the alarm hour is most common time IAL...

Страница 24: ...R ZONE SOUNDER ALARM OUTPUTS LOOP POWERED SOUNDERS ONLY MAINS FAILED CURRENT BUZZER ON 39mA MAINS FAILED CURRENT BUZZER OFF 37mA MAXIMUM LOOP RESISTANCE 25 ohms MAXIMUM LOOP CAPACITANCE 0 3 F MAXIMUM...

Страница 25: ...has a base sounder fitted mark the column with a tick or a Y Test each detector for Alarm operation Eg With smoke Spray and for fault reporting by removing the detector Check that each sounder operate...

Страница 26: ...RUCTION MANUAL 32 Device 4 Zone Addressable Fire Alarm Panel Approved Document No GLT MAN 129 PAGE 26 Issue 1 0 Author NRPJ Date 11 04 2008 Log Book MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR...

Страница 27: ...ssable Fire Alarm Panel Approved Document No GLT MAN 129 PAGE 27 Issue 1 0 Author NRPJ Date 11 04 2008 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT...

Страница 28: ...ION MANUAL 32 Device 4 Zone Addressable Fire Alarm Panel Approved Document No GLT MAN 129 PAGE 28 Issue 1 0 Author NRPJ Date 11 04 2008 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUD...

Отзывы: