PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK (Fyreye MKII) 

#Doc No. GLT-215-7-2 

 

PAGE 35

 

 

Issue: 1.08   Author: TE/NJ     Date: 26/05/2017

 

 

10. COMMISSIONING THE SYSTEM, INCLUDING POWER SUPPLY EQUIPMENT P.S.E. 

 

The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has an 
understanding of sections 2, 3, & 4 of BS 5839-1:2013 (i.e. Design considerations, Limitations of false alarms, Installation 
recommendations). 

 

The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer. 

 

The system set-up data chart (GLT.MAN-108, section 8) should be checked for accuracy. 

 

The fire alarm log book contact details should be checked for completeness. 

 

The insulation of cables should be checked in accordance with BS 5839-1:2013 clause 38.2 for compliance. 

 

The earthing should be checked in accordance with BS 5839-1:2013clause 38.2 for compliance. 

 

The PSE mains feed from a 3A spur should be checked. It should be protected by an over current device (MCB) NOT an 
earth leakage device (RCD). 

 

The PSE Charger voltage should be checked & adjusted if necessary (28.3 with batteries disconnected). 

 

The battery voltage should be checked (should be between 24 & 27V). 

 

All call points & detectors can signal an alarm condition and indicate the correct zone (and text message) on the fire alarm 
panel. 

 

The Sound pressure level throughout the building should be checked for compliance with the recommendations of BS 
5839-1:2013 clause 16.2. 

 

Any deviations from BS 5839-1:2013 clause 7.2 should be listed in the Certificate of Installation & Commissioning. 

 

The Certificate of Installation & Commissioning should be completed, and the whole user manual passed to the relevant 
person on site. (They should be given a brief training on the basic operation of the FACP). 

10.1 DESIGN, INSTALLATION & COMMISSIONING CERTIFICATES 

The guidelines in BS 5839-1:2013 say that each stage of the system design and installation should have a separate certificate. Before 
this User Manual is handed over to the relevant person(s) on site, the following certificates (or the relevant company’s equivalent) 
should be completed by the system designer, the installation engineer and the commissioning engineer. The System Description 
sheet should also be completed on Pages 12-20 as should the relevant parts of the Log Book section starting on Page 21. 

The user or responsible person should then complete the acceptance certificate to acknowledge that they have been instructed in 
the use of the fire alarm, have witnessed that it is operational, and have been given all the relevant paperwork (drawings, log book, 
user manual, etc.). 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Premier Quatro QT/4P

Страница 1: ...NCE GUIDE LOG BOOK Fyreye MKII Firmware Versions PANEL 1 84 LOOP CARD 3 70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK www acornfiresec...

Страница 2: ...CATES AN ALARM 8 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 8 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 8 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP TO EVACUATE THE BUILDING 9 5 5 RESETTING...

Страница 3: ...ivate a smoke detector If anything is found try to clear the room by opening a window If there is a fire discovered either attempt to douse it with a fire extinguisher if suitably trained or call the...

Страница 4: ...the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call Point 3 To split the...

Страница 5: ...ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are recorded with updated d...

Страница 6: ...ch Mode cage INPUT Voltage 30 5 VAC Charger Voltage 27 6V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only Carry out a complete...

Страница 7: ...the panel next to the enclosure s lock If the panel is located in a position where the general public have access this key must be removed from the panel and placed where it can be easily accessed by...

Страница 8: ...cel programmed delays and test the LEDs and LCD The user can also enter the test mode which permits points in selected zone s to be tested without causing the alarm to be raised throughout the buildin...

Страница 9: ...2nd point is located in zone 86 STAIRWELL The address label of this point is ROOM 101 It is on panel number 2 loop number 4 and at address 124 The point which is an optical detector was triggered at...

Страница 10: ...ers Note If ALL of the Alarm Sounders have been disabled pressing the STOP START BUTTON will have NO effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the cause of the alarm wa...

Страница 11: ...t of this are 20 LEDs which are used to indicate Zone Faults Disablement Test in Zones 1 20 COMMON FAULT The Common fault LED is lit for all types of fault SUPPLY FAULT This indicates a loss of Mains...

Страница 12: ...ght along with the zone that contains that sounder Because the sounder is addressable any fault will be indicated as a device fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the res...

Страница 13: ...r disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more input devices detector call point or i...

Страница 14: ...FIRE ALARM SYSTEM SUMMARY FIRE ZONE INFORMATION ZONE NO LOOP NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I...

Страница 15: ...ZONE NO LOOP NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 37 38 39 40 41 42 43 44 45 46 47 48 49 50 5...

Страница 16: ...NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 10...

Страница 17: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 1...

Страница 18: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 1...

Страница 19: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 2...

Страница 20: ...contained in each circuit NO OF SOUNDERS NO OF BELLS 1 2 INPUTS OUTPUTS INFORMATION ZONE NO LOOP NO DESCRIPTION OF INPUTS AND OUTPUTS CONNECTED TO LOOP WHAT HAPPENS WHEN ACTIVATED FIRE FAULT RELAYS IN...

Страница 21: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Страница 22: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Страница 23: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Страница 24: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Страница 25: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Страница 26: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Страница 27: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Страница 28: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Страница 29: ...work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fi...

Страница 30: ...K Fyreye MKII Doc No GLT 215 7 2 PAGE 29 Issue 1 08 Author TE NJ Date 26 05 2017 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED...

Страница 31: ...eye MKII Doc No GLT 215 7 2 PAGE 30 Issue 1 08 Author TE NJ Date 26 05 2017 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SI...

Страница 32: ...1 08 Author TE NJ Date 26 05 2017 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY...

Страница 33: ...Author TE NJ Date 26 05 2017 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATE...

Страница 34: ...7 2 PAGE 33 Issue 1 08 Author TE NJ Date 26 05 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIR...

Страница 35: ...PAGE 34 Issue 1 08 Author TE NJ Date 26 05 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION...

Страница 36: ...an signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compliance with the recommend...

Страница 37: ...onsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2013 for the system category described below except for the variations if any stated in t...

Страница 38: ...ided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken...

Страница 39: ...recommendations of BS 5839 1 2013 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signat...

Страница 40: ...ent operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of...

Страница 41: ...l installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete...

Отзывы: