7. DISABLEMENTS 

7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM 

Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if 
there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to 
disable that zone during the risk period and then enable it again afterwards. During a disablement of a zone(s), no fire or fault signal 
will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled, that is zones already in a fire condition cannot 
be disabled. 

External sounders can also be disabled as could be required in certain conditions 

7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS 

1.

 

Insert and turn control key to enabled position; 

2.

 

Press DISABLE button and the screen will show: 

ZONE DISABLEMENT ZONE 1. The panel is now in SELECT DISABLEMENT MODE. 

3.

 

Press DISABLEMENT SELECT until the required zone or sounder circuit is DISPLAYED. 
Press DISABLEMENT CONFIRM button.  
 
The screen will now show that the zone is disabled, and the Zone or Sounder LED will 
come on steady, along with the GENERAL DISABLEMENTLED. This section is now 
disabled.  

Zone Disablement 

Zone 1 

Zone Enabled 

Disabled Devices: 0 

  

Zone Disablement 

Zone 3 

Zone Disabled 

Disabled Devices: 0 

 

4.

 

If more than one zone (or sounder) needs to be disabled, then press DISABLEMENT SELECT again until the required zone 
(or sounder) is selected. 

5.

 

If the panel needs to be taken out of SELECT DISABLEMENT MODE (e.g. to silence a fault on another part of the system), 
Either press DISABLEMENT button, or turn the keyswitch off, then back on again.  

6.

 

Once all the maintenance work has been done the zones need to be enabled again. If the panel is still in SELECT 
DISABLEMENT MODE, jump to paragraph 7, otherwise, turn the keyswitch to controls enabled, press DISABLE button. The 
panel is now in SELECT DISABLEMENT MODE. 

7.

 

Press the DISABLEMENT SELECT button until the disabled zone is displayed on the screen. Press DISABLEMENT CONFIRM 
button to de-select disablement. Scroll to any other disabled zone and enable in the same way. When all zones are 
enabled again, the GENERAL DISABLEMENT LED will turn off. Turn the keyswitch to off position to return the system to 
normal. 

7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS 

1.

 

Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED with 
stay lit (steady); 

2.

 

Press DISABLE button and the screen will show: ZONE DISABLEMENT ZONE 1. The panel is now in SELECT DISABLEMENT 
MODE. 

3.

 

Press SELECT until the disabled Zone or sounder is shown. 

4.

 

Press CONFIRM to enable the selected item. The screen will now show enabled, and its disablement LED will turn off. The 
General Disablement LED will also turn off after all sections are taken out of disablement. 

5.

 

Turn control Key to “Off” position and this will return the panel to normal operation. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Simplicity Plus SP-64/M

Страница 1: ...are Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 Issue 3 09 Author NRPJ Date 25 5 2017 ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE L...

Страница 2: ...M SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES OF FAULT 8 6 2...

Страница 3: ...LARM PANEL SHOWS A FAULT YELLOW LED Write down the LCD reading and which LEDs are lit either in the log book or on a piece of paper for transferring to the log book later If the supply fault LED is li...

Страница 4: ...guished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operati...

Страница 5: ...eld on site 47 2 j 1 2 11 In the event of a pre alarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenance if the cause is a c...

Страница 6: ...as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in th...

Страница 7: ...ch device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code Th...

Страница 8: ...s will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SIGNAL...

Страница 9: ...ns failure or a battery failure The LEDs on the Power Supply charger PCB will help the service engineer pinpoint the source of the problem If the mains supply fails the panel will only operate for the...

Страница 10: ...s the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Take...

Страница 11: ...E GUIDE LOG BOOK Software Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 10 Issue 3 09 Author NRPJ Date 25 5 2017 6 3 OTHER LED INDICATIONS DISABLEMENTS TEST MODE www acornfires...

Страница 12: ...abled Devices 0 4 If more than one zone or sounder needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELEC...

Страница 13: ...as contained in each zone QTY SNDR QTY MCP QTY HEADS 1 2 3 4 5 6 7 8 OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED AUXILIARY OUTPUT YES NO FAULT OUTPUT YES NO ADDITIO...

Страница 14: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Страница 15: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Страница 16: ...work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fir...

Страница 17: ...PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 16 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL...

Страница 18: ...r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 17 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Страница 19: ...T MAN 108 PAGE 18 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Страница 20: ...108 PAGE 19 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINT...

Страница 21: ...oved Document No GLT MAN 108 PAGE 20 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE...

Страница 22: ...Document No GLT MAN 108 PAGE 21 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING C...

Страница 23: ...27V All call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked fo...

Страница 24: ...t the said design for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 for the system category described below ex...

Страница 25: ...s applicable for min Appropriate guidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recomme...

Страница 26: ...ith the specifications described below and with the recommendations of BS5839 1 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of...

Страница 27: ...endations of BS 5839 1 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accord...

Страница 28: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...

Страница 29: ...7 2012 Updated images Fixed Formatting 3 06 26 7 2012 Fixes Table Errors Corrected references to Quatro Panel to Simplicity Panel Moved Modification History back to first page Realigned Page Breaks U...

Отзывы: