SIMPLICITY PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Software Versions: PANEL r7255 & LOOP r7152
Approved Document No: GLT.MAN-108
PAGE 5
Issue 3.09 Author: NRPJ Date: 25/5/2017
4. PANEL INDICATIONS & CONTROLS
4.1 PANEL INDICATIONS
The Simplicity has been designed to be as straight forward as possible. To help achieve this it has been designed so that its LEDs are
the primary display. Every possible fault has its own unique LED. Each LED is used to represent only one condition. This helps avoid
the confusion caused when a single LED is used for 2 or more conditions. The LCD is only used during setup, and to give detailed
information about zone faults.
4.2 PANEL CONTROLS
The controls on the Simplicity are grouped together to try to be as user friendly as possible. The Silence, Reset & Start/Stop Sounder
buttons are the main control buttons. The previous & Next buttons by the LCD are used to scroll between fault messages. The next
button is also used in the Device Status Menu. The General Test, Select & Confirm buttons are used to control the one man test
mode. The General Disablement, Select & Confirm buttons are used to select panel section disablements. The numeric section is for
entering access codes, and for entering device addresses. The alphabet keys are used to enter device labels in the programming
menu.
4.3 IN THE EVENT OF AN ALARM
After the site has been deemed safe for return, to return the panel to normal: -
1.
Turn keyswitch to Controls access on position.
2.
Press Stop/Start = turn off external sounders
3.
Press Silence = turn off the panels buzzer
4.
Record the LCD details in the Fire Alarm Log Book
5.
Press Reset = return panel to normal condition.