Installation – 

Mounting Height & Clearance

6

www.zephyronline.com

DUCTING

A minimum of 6” round duct must be used to 
maintain maximum air fl ow effi ciency.

Always use rigid type metal ducts only. Flexible 
ducts could restrict air fl ow by up to 50%.

Use calculation worksheet to compute total duct 
work (Page 5).

ALWAYS, when possible, reduce the number of 
transitions and turns. If a long duct run is required, 
increase duct size from 6” to 7” or 8”.

If turns or transitions are required: Install as far 
away from duct opening and as far apart between 
the two transitions as possible.

Minimum mount height between range top to hood 
bottom should be no less than 26”.

Maximum mount height should be no higher than 
34”.

It is important to install the hood at the proper 
mounting height. Hoods mounted too low could 
result in heat damage and fi re hazard; while hoods 
mounted too high will be hard to reach and will 
loose performance and effi ciency.

If available, also refer to range manufacturer’s 
height clearance requirements and recommended 
hood mounting height above range. Always check 
your local codes for any differences.

Duct cover extension kit available for ceiling 
heights up to 12 feet. Turn to page 16 for part 
number and ordering information.

DAMAGE-SHIPMENT / INSTALLATION:

•  Please fully inspect unit for damage before 

installation.

•  If the unit is damaged in shipment, return the 

unit to the store in which it was bought for 
repair or replacement.

•  If the unit is damaged by the customer, repair 

or replacement is the responsibility of the 
customer.

•  If the unit is damaged by the installer (if other 

than the customer), repair of replacement must 
be made by arrangement between customer 
and installer.

min.  A
min.  B
max. C

    

 

 

 

Standard  

Extension

Hood Heights  

 

Duct Cover 

Duct Cove

r

            minimum ducted (A)  28” 

 

50 

1/2

 minimum recirculating (B)  32” 

 

54 

1/2

                          maximum (C)  39” 

 

79”

Ceiling Heights

           minimum ducted (D)  90” (7’ 6”) 

112“ (9’ 4”)

 minimum recirculating (E)  94” (7’ 10”) 

116“ (9’8)

                          maximum (F)  109” (9’ 1“)        149” (12’ 5”)

36”

26” min.

34” max.

min.  D
min.  E
max. F

Содержание Roma Island ZRM-E36BS

Страница 1: ...Use Care and Installation Guide Model number Serial Number www zephyronline com Roma Island ZRM E36BS ZRM E42BS ZRM E36BS290 ZRM E42BS290 JAN13 0301...

Страница 2: ...www zephyronline com...

Страница 3: ...ght Clearance 6 Ducting Options 7 Hood Speci cations 8 Mounting the Hood 9 10 Ductless Recirculating 11 FEATURES CONTROLS Electronic LED Controls 12 MAINTENANCE Hood and Filter Cleaning 13 Light Bulbs...

Страница 4: ...te for the type of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close tting lid cook...

Страница 5: ...al installation is adequate and in conformance with National Electrical Code ANSI NFPA 70 latest edition or CSA standards C22 1 94 Canadian Electrical Code Part 1 and C22 2 No 0 M91 latest edition and...

Страница 6: ...6BS ZRM E42BS ZRM E36BS290 ZRM E42BS290 PARTS SUPPLIED HARDWARE PACKAGE CONTENTS PARTS NOT SUPPLIED Ducting conduit and all installation tools Hack saw to cut down trim pieces Cable connector if requi...

Страница 7: ...ent number length x used 6 8 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 or 8 Round 900 elbow 15 Ft x Ft 7 or 8 7 or 8 Round 450 elbow 9 Ft x Ft Ft Ft Ft 6 8 Round ro...

Страница 8: ...ose performance and ef ciency If available also refer to range manufacturer s height clearance requirements and recommended hood mounting height above range Always check your local codes for any diffe...

Страница 9: ...ed to the outside unless using the recirculating option Use single wall rigid metal ductwork only Fasten all connections with sheet metal screws and tape all joints w certi ed Silver Tape or Duct Tape...

Страница 10: ...ine com Installation Hood Speci cation CL 35 7 8 41 7 8 14 3 15 16 26 15 16 STANDARD min ducted 28 min recirc 32 max 39 Z1C 01RM EXTENSION min ducted 50 1 2 min recirc 54 1 2 max 79 12 3 1 2 4 1 8 5 6...

Страница 11: ...ord front on the top support frame faces the front of the hood where the controls will be located FIG D The key holes on the top support frame should cover the wood screws previously installed in the...

Страница 12: ...x 1 4 screws FIG D2 9 Assemble Bottom Duct Covers together over top duct covers using the nal 6 M3 x 6 screws 3 screws on each side of the duct cover FIG D3 Bottom Duct Covers should rest on top of t...

Страница 13: ...REQUIRED IF NO DUCTING IS USED Kit includes charcoal lters brackets and air diverter plate Hood Models Part No Filters Brackets in pkg ZRM E36BS ZRC 00RM 2 ZRM E42BS ZRC 01RM 3 1 Purchase recirculatin...

Страница 14: ...If lights are on they will also switch off when this button is pressed These controls feature a memory function that will remember the last setting before being powered off For example If blower is o...

Страница 15: ...on cloth and with the grain Do not use any product containing chlorine bleach Do not use orange cleaners Aluminum Mesh Filters The aluminum mesh lters installed by the factory are intended to lter out...

Страница 16: ...ot hot Remove by turning bulb counter clockwise Note Bulb does not unscrew it turns 60 degrees stops and falls out If bulbs are dif cult to turn due to prolonged use rmly attach the included glass suc...

Страница 17: ...stallation of the hood The unit is whistling 1 The lter is not in the correct position 1 Adjust the lters 2 The duct pipe connections are not sealed or connected properly 2 Check the duct pipe connect...

Страница 18: ...16 www zephyronline com Wiring Diagrams...

Страница 19: ...20 Aluminum Mesh Filter each 50200038 Optional Accessories Recirculating Kit ZRM E36BS ZRC 00RM Recirculating Kit ZRM E42BS ZRC 01RM Replacement Charcoal Filter each Z0F C002 Extension Duct Cover Z1C...

Страница 20: ...all labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR OPTION SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY WE SHALL NOT BE LIA...

Страница 21: ...Guide d utilisation d entretien et d installation www zephyronline com Num ro de mod le Num ro de s rie JAN13 0301 Zephyr Corporation Roma Island ZRM E36BS ZRM E42BS ZRM E36BS290 ZRM E42BS290...

Страница 22: ...www zephyronline com...

Страница 23: ...montage 6 Options d installation pour le conduit 7 Sp ci cations de la hotte 8 Montage de la hotte 9 10 Reprise d air sans conduit 11 COMMANDES Commandes lectroniques DEL 12 ENTRETIEN Nettoyage des lt...

Страница 24: ...s surveillance lorsque vous cuisinez h Utilisez toujours une batterie de cuisine et des ustensiles convenant au type et la quantit de nourriture que vous pr parez AVERTISSEMENT POUR R DUIRE LES RISQUE...

Страница 25: ...en quali S assurer que l installation lectrique est ad quate et qu elle respecte le Code national de l lectricit la plus r cente dition du ANSI NFPA 70 ou des normes du CSA C22 1 94 le Code canadien d...

Страница 26: ...Liste du mat riel 4 www zephyronline com...

Страница 27: ...pi x pi embout mural circ registre 30 pi x pi 7 or 10 circ coude 90 15 pi x pi 7 or 10 7 or 10 circ coude 45 9 pi x pi pi pi pi 6 chapeau de toiture circ 30 pi x pi 7 or 10 circ chapeau de toiture 30...

Страница 28: ...pr senter des risques d incendie plus lev s tandis que les hottes install es trop hautes seront dif ciles atteindre et verront leur ef cacit et leur rendement r duits Si elles sont disponibles consult...

Страница 29: ...ppements doivent tre dirig s l ext rieur de la maison moins que l option de reprise d air ne soit utilis e N utilisez que des conduits en m tal pour cloison simple Fixez toutes les pi ces du conduit a...

Страница 30: ...8 www zephyronline com Installation Sp ci cations de la hotte...

Страница 31: ...cadre de xation sup rieur l emplacement d sir au plafond l aide de quatre 4 rondelles et vis bois M4 x 1 1 2 Une vis devrait tre ajout e chaque coin pour xer le cadre de xation au plafond FIG A2 Le ca...

Страница 32: ...r avant d assembler les pi ces de recouvrement de conduit Consultez la page 11 pour de plus amples d tails 8 Fixez les pi ces de recouvrement sup rieures au cadre de xation sup rieur l aide de 2 vis 3...

Страница 33: ...mprend des ltres charbon des supports et un d ecteur d air Mod le de hotte Num ro de pi ce Filtres et supports par paquet ZRM E36BS ZRC 00RM 2 ZRM E42BS ZRC 01RM 3 1 Procurez vous l ensemble de repris...

Страница 34: ...12 www zephyronline com Commandes Commandes lectroniques DEL...

Страница 35: ...et dans le sens du grain N utilisez pas de produits blanchir au chlore ou d agents nettoyants orange Filtres tamis en aluminium Les ltres tamis en aluminium install s par le fabricant ont pour foncti...

Страница 36: ...s d vissant dans le sens contraire des aiguilles d une montre Note les ampoules ne se d vissent pas apr s une rotation de 60 degr s elles s arr tent et tombent de la douille Lorsqu il est dif cile de...

Страница 37: ...appareil vibre 1 Le moteur n est pas bien x en place 1 Fixez solidement le moteur en place 2 La roue du ventilateur est endommag e 2 Remplacez le ventilateur 3 La hotte n est pas bien x e en place 3...

Страница 38: ...16 www zephyronline com Sch ma de c blage...

Страница 39: ...00038 Accessoires optionnels Ensemble de reprise d air ZRM E36BS ZRC 00RM Ensemble de reprise d air ZRM E42BS ZRC 01RM Filtres charbon de remplacement chaque Z0F C002 Ensemble de prolongement de recou...

Страница 40: ...main d uvre associ s la pr sente garantie Restrictions de la garantie NOTRE OBLIGATION DE R PARER OU DE REMPLACER NOTRE GR LE PRODUIT CONSTITUE VOTRE SEUL ET UNIQUE RECOURS SOUS LA PR SENTE GARANTIE...

Отзывы: