inBOX 24 vT / inBOX 20 vT
Technical Support:
21
ANNEX I. COMMUNICATION OBJECTS INBOX 20 VT
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5, 16
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Ox] Scenes
0
–
63 (Execute 1
–
64); 128
–
191 (Save 1
–
64)
6, 17
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.O. (0=Open Relay; 1=Close
Relay)
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.C. (0=Close Relay; 1= Open
Relay)
7, 18
1 Bit
O
C R - T -
DPT_BinaryValue
0/1
[Ox] On/Off (Status)
0=Output Off; 1=Output On
8, 19
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ox] Lock
0=Unlock; 1=Lock
9, 20
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Timer
0=Switch Off; 1=Switch On
10, 21
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Flashing
0=Stop; 1=Start
11, 22
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Normal; 1=Alarm
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Alarm; 1=Normal
12, 23
1 Bit
I
C - W - -
DPT_Ack
0/1
[Ox] Unfreeze Alarm
Alarm=0 + Unfreeze=1 => End
Alarm
13, 24
1 Bit
O
C R - T -
DPT_State
0/1
[Ox] Warning Time (Status)
0=Normal; 1=Warning
14, 25
4 Bytes
I/O
C R W T -
DPT_LongDeltaTimeSec
-2147483648 -
2147483647
[Ox] Operating Time (s)
Time in Seconds
15, 26
2 Bytes
I/O
C R W T -
DPT_TimePeriodHrs
0 - 65535
[Ox] Operating Time (h)
Time in Hours
27
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Shutter] Scenes
0 - 63 (Execute 1 - 64); 128 - 191
(Save 1 - 64)
28
1 Bit
I
C - W - -
DPT_UpDown
0/1
[CA] Move
0 = Raise; 1 = Lower
29
1 Bit
I
C - W - -
DPT_Step
0/1
[CA] Stop/Step
0 = Stop/StepUp; 1 =
Stop/StepDown