Airbreak Installation.
Set Up Water Discharge
Single stall
Single trough
Maximum trough
Width 600 mm
Typical Installation with Direct Injection: Model WS005
The air break must be fitted in a vertical position. Fitting in a position other
than vertical will result in leakage.
Fit the air break to the top of the urinal sparge pipe (in place of a cistern),
as shown in the diagram. Locate as high as possible.
Do not use sealing tape in the air break joints. The fittings in the latching
valve will require the use of sealing tape.
Supply and install a half-inch pipe from the top of the air break, to the
outlet side of the latching valve.
Securely fix the piping to the wall as per AS/NZS3500 to prevent possible
tampering and vandalism.
Sensor
latching Valve
Isolating Valve
Direct injection
air break
Sensor
latching Valve
Isolating Valve
Direct injection
air break