SPA-V2 Public Address & General Alarm System
Installation & Configuration Manual
A100K10370
9
SPA-EE3D-V2 alarm generator (second)
-
Start alarms from Alarm panels – X16/17
-
GA
-
Abandon
-
Manual/Fire
-
Reset Alarms
-
Start Fire All and Crew / Engine Room – X16/17
-
All zones
-
Select zones by setting jumper J5 to required zones
-
Select required PROM setup according to section 2.11 by operating the PROM selector on the EE3 board
-
Test that PA mutes alarms
-
Test the main and standby function by disconnecting the 1x8 RJ45 plug on main Alarm generator. The LED on main generator
will change from blinking to steady and the standby alarm generator will start to blink. This indicates that the standby alarm
generator is active.
10
Priority Input
Test that the system has the following priorities:
-
Talk-Back: 1
st
priority
-
Mic Panels: 2
nd
to 4
th
priority.
-
PABX: 5
th
priority.
-
Alarm: 6
th
priority
-
Entertainment: 7
th
priority
Alarm priority can be changed by setting the jumpers J9 to J16 on main terminal board.
Alarm has ____ priority.
11
100 V Speaker output on the main terminal board X14
Test that we have 100V AC Speaker output up to 6 x Zone relay. Use an impedance meter for measuring speaker load.
Maximum load connected to the different amplifiers:
-
83 ohm – 120 W amplifiers
-
42 ohm – 240 W amplifiers
-
25 ohm – 400 W amplifiers
12
100 V Speaker output on SPA multi zone board - SPA-MUL-V2
Test that we have 100V speaker audio output up to 3 x (6 x Zone relay).
Maximum load connected to the different amplifiers:
-
83 ohm – 120 W amplifiers
-
42 ohm – 240 W amplifiers
-
25 ohm – 400 W amplifiers
13
Make a PA message from a Talk-Back panel
Follow instructions in the
SPA-V2 User Manual
, section 2.10
L
If other signal levels are required after installation, adjust the signal by using trimming potentiometer marked
P1 CTB/ETB VOL for audio from Talk-Back System on main terminal board, block X7
Additional function boards for the SPA system
14
Ding-dong chime generation - SPA-CHIME-V2
This multiple chime generator has a setting for tone.
-
Set the required tone by operating the potentiometer for tone selection.
-
Set the tone level to 40 VAC by operating the potentiometer for volume setting.
15
Start entertainment unit - SPA-RCD
-
Switch on “ENTERTAINMENT ON/OFF”
-
Follow user instructions for delivered model.
16
Start Entertainment monitor/control unit - SPA-SWITCH-V2
This unit has an adjustable preamplifier.
-
For system with entertainment sources such as SPA-RCD6, SPA FM/AM
-
Follow instructions in the SPA-V2 User Manual.
17
Interface to external system – SPA-EMS-V2
Additional terminal board for interface Emergency PA and alarm to external system set by jumpers.
-
Test that only EMS and Alarm activate Emergency output signal 0 dB and potential-free contact to external system J1 – X80
-
Test that EMS and ALL CALL, and alarm activate Emergency output signal 0 dB and potential-free contact to external system
J1 – X80
18
Make a PA message using digital message recorder unit combined with remote panel SPA-REM7
-
See separate instructions for digital message recorder unit
19
Test of 4-way volume control function (Override) - use board SPA-MUL-V2
Follow instructions in the
SPA-V2 User Manual
.
Volume Override can be changed via jumper settings:
-
PA override by zone selection or only “All Call” is set with jumper J24 on the main terminal board
-
For EMS or PA and EMS
ONLY
volume control override is set with jumpers J37/J7 on the SPA-MUL-V2 / SPA-ENT4-V2 board