SPA-V2 Public Address & General Alarm System

Installation & Configuration Manual

A100K10370

9

SPA-EE3D-V2 alarm generator (second)

 

-

Start alarms from Alarm panels – X16/17

 

-

GA

 

-

Abandon

 

-

Manual/Fire

 

-

Reset Alarms

 

-

Start Fire All and Crew / Engine Room – X16/17

 

-

All zones

 

-

Select zones by setting jumper J5 to required zones

 

-

Select required PROM setup according to section 2.11 by operating the PROM selector on the EE3 board

 

-

Test that PA mutes alarms

 

-

Test the main and standby function by disconnecting the 1x8 RJ45 plug on main Alarm generator. The LED on main generator 

will change from blinking to steady and the standby alarm generator will start to blink. This indicates that the standby alarm 

generator is active.

10

Priority Input

Test that the system has the following priorities:

 

-

Talk-Back: 1

st

 priority

 

-

Mic Panels: 2

nd

 to 4

th

 priority.

 

-

PABX: 5

th

 priority.

 

-

Alarm: 6

th

 priority

 

-

Entertainment: 7

th

 priority

Alarm priority can be changed by setting the jumpers J9 to J16 on main terminal board.

Alarm has ____ priority.

11

100 V Speaker output on the main terminal board X14

Test that we have 100V AC Speaker output up to 6 x Zone relay. Use an impedance meter for measuring speaker load.

Maximum load connected to the different amplifiers:

 

-

83 ohm – 120 W amplifiers

 

-

42 ohm – 240 W amplifiers

 

-

25 ohm – 400 W amplifiers

12

100 V Speaker output on SPA multi zone board - SPA-MUL-V2

Test that we have 100V speaker audio output up to 3 x (6 x Zone relay).

Maximum load connected to the different amplifiers:

 

-

 83 ohm – 120 W amplifiers

 

-

42 ohm – 240 W amplifiers

 

-

25 ohm – 400 W amplifiers

13

Make a PA message from a Talk-Back panel

Follow instructions in the 

SPA-V2 User Manual

, section 2.10

 

L

If other signal levels are required after installation, adjust the signal by using trimming potentiometer marked 

P1 CTB/ETB VOL for audio from Talk-Back System on main terminal board, block X7

Additional function boards for the SPA system

14

Ding-dong chime generation - SPA-CHIME-V2

This multiple chime generator has a setting for tone.

 

-

Set the required tone by operating the potentiometer for tone selection.

 

-

Set the tone level to 40 VAC by operating the potentiometer for volume setting.

15

Start entertainment unit - SPA-RCD

 

-

Switch on “ENTERTAINMENT ON/OFF”

 

-

Follow user instructions for delivered model.

16

Start Entertainment monitor/control unit - SPA-SWITCH-V2

This unit has an adjustable preamplifier.

 

-

For system with entertainment sources such as SPA-RCD6, SPA FM/AM

 

-

Follow instructions in the SPA-V2 User Manual.

17

Interface to external system – SPA-EMS-V2

Additional terminal board for interface Emergency PA and alarm to external system set by jumpers.

 

-

Test that only EMS and Alarm activate Emergency output signal 0 dB and potential-free contact to external system J1 – X80

 

-

Test that EMS and ALL CALL, and alarm activate Emergency output signal 0 dB and potential-free contact to external system 

J1 – X80

18

Make a PA message using digital message recorder unit combined with remote panel SPA-REM7

 

-

See separate instructions for digital message recorder unit

19

Test of 4-way volume control function (Override) - use board SPA-MUL-V2

Follow instructions in the 

SPA-V2 User Manual

.

Volume Override can be changed via jumper settings:

 

-

PA override by zone selection or only “All Call” is set with jumper J24 on the main terminal board

 

-

For EMS or PA and EMS 

ONLY

 volume control override is set with jumpers J37/J7 on the SPA-MUL-V2 / SPA-ENT4-V2 board

Содержание Vingtor Stentofon SPA-AC6

Страница 1: ...icrophone Alarm panel Alarm panel Entertainment LS zone 5 LS zone 6 Engine area Open deck GENERAL ABANDON MANUAL RESET EMS SPARE SPA A6CD 1 2 3 4 5 6 ALL SPA M6D TALK DIM Open deck ACM Integrated Syst...

Страница 2: ...ng SPA M1 V2 SPA AC6 15 2 7 4 Connecting SPA M1 D SPA AC6 D 16 2 7 5 Connecting SPA M6 SPA AC6 17 2 7 6 Connecting SPA M6 D SPA AC6 D 18 2 7 7 Connecting SPA W1 V2 19 2 7 8 Connecting SPA W1 D 19 2 7...

Страница 3: ...3 Commissioning 47 3 1 General 47 3 2 Mechanical Inspection 47 3 3 Cable Connection Inspection 47 3 4 Power Supply Consumption Check 47 3 5 Function Configuration Check 47 3 6 Startup Procedure 48 4...

Страница 4: ...ings in AutoCAD Amplifier and Entertainment manuals 1 4 Rules and Regulations The SPA V2 Public Address and General Alarm System is designed to meet the requirements in accordance with SOLAS Section I...

Страница 5: ...he carton carefully remove the contents and check for any signs of mechanical damage The SPA delivery package can depending on the order contain the following equipment see attached packing list Rack...

Страница 6: ...comply with SOLAS Ch II 1 45 5 2 The PA system has been fully tested and fulfills all requirements according to EN 60945 and IACS E10 standard Cables for service required to be operable under fire con...

Страница 7: ...MASTER VOLUME POWER 10 10 0 10 10 10 0 0 5 OUTPUT LEVEL OVERL ON dB 40 12 6 0 1 SERIES POWER AMPLIFIER I 0 BASS TREBLE MASTER VOLUME POWER 10 10 0 10 10 10 0 0 5 OUTPUT LEVEL OVERL ON dB 40 12 6 0 1...

Страница 8: ...here are four 12 mm fastening holes for mounting the rack to the floor as standard There are air ventilation slots on both sides and rear of all units Free space on both sides should be minimum 300 mm...

Страница 9: ...n Configuration Manual A100K10370 2 6 2 Microphone Panels Indoors SPA M1 V2 SPA M1 D SPA M6 V2 SPA M6 D L SPA M1 V2 version are equipped with 2x cable gland PG 16 2 6 3 SPA M6BOKS For SPA M1 and SPA M...

Страница 10: ...A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 6 5 ACBOKS For SPA AC6 and SPA AC6 D when wall mounted 2 6 6 SPA W1 V2 SPA W1 D Weatherproof PA Panels 96 66...

Страница 11: ...A V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 6 7 SPA W1AR V2 SPA W1AR D Weatherproof PA and alarm panel 2 6 8 SPA W6A4 SPA W6A4 D Weatherproof PA and alarm p...

Страница 12: ...tion Configuration Manual 2 6 9 SPA REM7 Remote panel for message recorder 2 6 10 SPA BOXM1 For VM15 R and VM50 R when wall mounted 2 6 11 VM15 RD VM50 RD VM15 RDF VM50 RDF Volume Controls 5 96 17 5 8...

Страница 13: ...d the SPA rack Typical system configurations are shown at the end of this section All drawings are also available in AutoCAD 2 7 1 Connecting Power Supply 1 230V AC main and 24V DC emergency Figure 4...

Страница 14: ...m System Installation Configuration Manual 2 7 2 Connecting Power Supply 2 230V AC main and 230 V AC emergency with failure unit SPA FAIL Figure 5 230 230 VAC with SPA FAIL board SHIP S EMERGENCY 230V...

Страница 15: ...15 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 3 Connecting SPA M1 V2 SPA AC6...

Страница 16: ...16 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 4 Connecting SPA M1 D SPA AC6 D...

Страница 17: ...17 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 5 Connecting SPA M6 SPA AC6...

Страница 18: ...18 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 6 Connecting SPA M6 D SPA AC6 D...

Страница 19: ...19 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 7 Connecting SPA W1 V2 2 7 8 Connecting SPA W1 D...

Страница 20: ...20 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 9 Connecting SPA W1AR V2...

Страница 21: ...21 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 10 Connecting SPA W1AR D...

Страница 22: ...22 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 11 Connecting SPA W6A4...

Страница 23: ...23 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 12 Connecting SPA W6A4 D...

Страница 24: ...24 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 13 Connecting Loudspeaker in Single System...

Страница 25: ...F X14 11 12 10 9 8 6 7 5 3 4 2 1 ZONE 1 F 100V LINE OUT X14 ZONE 2 0 ZONE 3 F ZONE 3 0 ZONE 4 F ZONE 4 0 ZONE 5 F ZONE 5 0 ZONE 6 F ZONE 6 0 3 4 2 1 24V 3 4 2 1 24V 24V 24V X61 SPA ENT4 V2 1 2 6 5 4...

Страница 26: ...26 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 15 Connecting Loudspeaker Volume Controls in A B System in Two Racks...

Страница 27: ...2 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 2 1 1 2 3 4 5 6 1 2 3 1 2 3 1 2 3 1 2 3 4 5 NO NC N F F O F F O F F O A30 1 2 3 4 5 6 7 8 9 10 11 1...

Страница 28: ...28 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 18 Configuration Example 1 Microphone panels PABX...

Страница 29: ...29 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 19 Configuration Example 2 Microphone Alarm Panels PABX...

Страница 30: ...30 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 20 Configuration Example 3 Dual PA GA...

Страница 31: ...31 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 21 Configuration Example 4 Required PA GA Connection between Racks 1 2...

Страница 32: ...2 and PRIO 3 in upper N position and PRIO 4 in lower position X4 X5 X6 X7 X8 X11 X15 X14 X13 X2 X1 EXTERN AMPLIFIER PA MUTE POTFREE OUTPUT ENTERT OUTPUT AUDIO OUT TO AMPLIFIER ALARM INPUT 1 PABX INPU...

Страница 33: ...igure 10 Jumpers for fire crew alarm per zone Zone selection for PABX Default setting PABX audio to all zones right position If PABX audio shall be distributed to different zones the jumper must be se...

Страница 34: ...ntertainment board 990 363 or J37 on the SPA multi 4 way entertainment 6 zones board have to be set to Normal and Emergency or Emergency Only This setting will override volume control The default sett...

Страница 35: ...N Disconnect ENT zone s by DIPSWITCH to position ENT Select the PA zone s 1 6A by DIPSWITCH to position ON Disconnect ENT zone s by DIPSWITCH to position PA Entertainment Public address output selecti...

Страница 36: ...rminal block X10 2 9 3 Signal Adjustment PABX Input Trim potentiometer marked P5 PABX VOL for audio input from Automatic Telephone System on terminal block X11 1 2 2 9 4 Signal Adjustment Entertainmen...

Страница 37: ...the number of loudspeakers and do the power tappings in accordance with available output power for the zone Make sure to NOT exceed the total amplifier output capacity Power tapping options can be fo...

Страница 38: ...of frequency must be undertaken by Zenitel personnel at customer site or the ship yard The procedure for changing the frequency is Change the value of the register OCR2 of the micro controller on one...

Страница 39: ...ched SPA AL REL6 V2 Steady Button 4 N A N A constantly Button 5 Press and hold Release Latched N A N A The MANUAL button is also used to manually generate alarm tone patterns 2 11 5 Alarm 2 L Refer to...

Страница 40: ...SPA AL REL6 V2 Steady constantly Button 4 Press and hold Release MOB Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 7 Alarm 4 L Refer to the SPA AL REL V2 and SPA REL...

Страница 41: ...Latched SPA AL REL6 V2 Steady constantly Button 4 Press and hold Release MOB Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 9 Alarm 6 L Refer to the SPA AL REL V2 and...

Страница 42: ...anual Release Manual Latched SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 11 Alarm 8 L Refer to the SPA AL REL V2 and SPA...

Страница 43: ...hed SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 13 Alarm 10 L Refer to the SPA AL REL V2 and SPA REL V2 figures in secti...

Страница 44: ...l Release Manual Latched SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 15 Alarm 12 L Refer to the SPA AL REL V2 and SPA RE...

Страница 45: ...AL REL6 V2 Steady Button 4 Press and hold MOB Release Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 17 Alarm 14 L Refer to the SPA AL REL V2 and SPA REL V2 figures in...

Страница 46: ...g 800 810Hz Woobling 3 Manual Continuous 800Hz Continuous 4 MOB 1 x long 1 short 800Hz 1s Short 3s Long 5 Abandon LED Manual LED MOB LED SPA AC6 Activation button Termination button Activation type Co...

Страница 47: ...re signal cables 0 75 mm2 approved ship cable of type twisted pair with outer braided copper shield Check that the shields are interconnected in junction boxes if used and grounded in ground terminals...

Страница 48: ...ttings are MASTER VOLUME to approximately 80 BASS and TREBLE to 0 position BMG to 0 position Chime OFF Chime volume 0 Switch ON amplifier Type EA1400 EA1600 Check that the Power LED is lit Fault and L...

Страница 49: ...low instructions in the SPA V2 User Manual section 2 10 L If other signal levels are required after installation adjust the signal by using trimming potentiometer marked P1 CTB ETB VOL for audio from...

Страница 50: ...output that is connected to the coil of the relay This triggers when only this panel is activated giving an active 24VDC out which breaks the audio going to the local speaker s Local mute outputs are...

Страница 51: ...SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 5 Appendix B Custom Alarm Configuration Example The configuration example shown below is for a standard 4002 Ala...

Страница 52: ...alarm time s 805 frequency Hz 0 800 Start alarm time s GENERAL ALARM ABANDON 500 1K 1 5K frequency Hz 0 800 Start alarm time s MANUAL FIRE Stop alarm LATCHED START PULSE START PULSE STOP Start alarm...

Страница 53: ...alarm time s Stop alarm 1s 1s 1s 1s repeating sequence ABANDON GERMAN FLAG MUSTER ABANDON NORSOK PFEER 500 1K 1 5K frequency Hz 1 2K repeat sequence 1s 1s 1s 1s 1s 1s 1s 1s 1s 500 1K 1 5K frequency Hz...

Страница 54: ...writing with Zenitel Any authorized reproduction in part or in whole must include this legend Zenitel All rights reserved The WEEE Directive does not legislate that Zenitel as a producer shall collec...

Отзывы: