Commissioning
3.1 General
The SPA system and all field equipment have been fully tested prior
to delivery. To ensure that everything is in order after installation and
configuration of the system, carry out the procedures described in the
following sections before using the system.
L
See section 2 Installation & Configuration Procedures.
3.2 Mechanical Inspection
●
Check that the cabinet is installed in a secure environment and well
fastened to the floor (and wall) in accordance with section 2.6.1
● Check that all field equipment is installed and well fastened in
accordance with section 2.6.2
●
Check that all equipment in the cabinet is undamaged after
installation.
● Check that all field equipment is undamaged after connecting the
cables.
3.3 Cable Connection Inspection
●
Check that all cables are connected in accordance with section 2.7.
●
Check that these are signal cables 0.75 mm
2
approved ship cable of
type twisted-pair with outer braided copper shield.
● Check that the shields are interconnected in junction boxes (if used)
and grounded in ground terminals in the cabinet only.
●
Check that the installation cables and glands are well fastened.
3.4
Power Supply/Consumption Check
●
Check that the power supply is used in accordance with
requirements in section 2.5.
●
Check that the total power consumption of the speaker network is
calculated and adjusted against available amplifier power.
3.5
Function Configuration Check
The configuration is normally done according to project specification
at delivery but may be changed if modifications are needed after
installation. Configuration settings affect functions such as routing and
adjusting the audio, determining some priorities, selecting zones, and
handling emergency calls.
●
Check that jumper settings are set in accordance with section 2.8.1
for the main terminal board.
●
Check that jumper settings are set in accordance with section 2.8.2 –
2.8.5 for additional function boards.
●
Check that the volume for audio input is adjusted in accordance with
section 2.9