3.11  Advanced mode

In the basic mode you have limited control 
over the units automated control options. In 
the advanced mode you can set many 

automated control options to your needs. You can 
find all these settings in the menu ADVANCED 
SETTINGS2. This menu is only accessible when the 
unit is in advanced mode.

3.11.1  Switch between basic and advanced mode

When in basic mode:
1.  Select SHIFT in the main screen.
2. Select ADVANCED.

When in advanced mode:
1.  Select SHIFT in the main screen.
2. Select BASIC.

SHIFT

MENU

200

m

3

/h

AUTO

BYPASS

Mo 14:02

BYPASS OPEN

min

50

SERVICE MODE

18.0

20.0

BASIC

MENU

200

m

3

/h

AUTO

BYPASS

Mo 14:02

BYPASS OPEN

min

50

SERVICE MODE

18.0

20.0

1

1

3.11.2  SENSOR VENTILATION2

In the SENSOR VENTILATION2 menu 
you can influence the following control 
functions which automatically increase 

the airflow setting (demand control) under favourable 
conditions.

Each control function can be set to:

Menu item

Function

ON

The unit will respond to the 
control function in AUTO and 
MANUAL mode. 

AUTO ONLY

The unit will only respond to 
the control function in AUTO 
mode.
When the unit is switched 
to manual mode the unit 
will deactivate this control 
function.

OFF

The unit will deactivate this 
control function.

TEMPERATURE PASSIVE2

The TEMPERATURE PASSIVE2 control can  be used 
to temper the indoor temperature by ventilating on 
airflow PRESET 3. The TEMPERATURE PASSIVE2 
control will activate airflow PRESET 3 when the 
following conditions are met:
-  TEMPERATURE PASSIVE2 control is permitted;
-  For MANUAL mode setting ON;
-  For AUTO mode setting AUTO ONLY or ON.
-  It is cooling season;
-  The indoor temperature is significantly higher than 

the temperature outside;

-  The bypass control is in AUTO mode;
-  The ComfoCool is turned off;
-  The unit has not been turned off within last two 

minutes;

-  Both fans are working;
-  The extract and supply temperature sensor are 

working.

This functions is set to OFF by default.

HUMIDITY COMFORT2

The HUMIDITY COMFORT2 control can be used 
to keep the indoor air quality at an acceptable 
level, based on absolute humidity. The HUMIDITY 
COMFORT2 control will increase the airflow when 
the following conditions are met:
-  HUMIDITY COMFORT2 control is permitted;
-  For MANUAL mode setting ON;
-  For AUTO mode setting AUTO ONLY or ON.
-  The indoor humidity is higher than the reference 

humidity;

-  The unit has not been turned off within last two 

minutes.

This functions is set to OFF by default.

HUMIDITY PROTECTION2

The HUMIDITY PROTECTION2 control can be 
used to protect the house against high humidity 
by ventilating on airflow PRESET 3. The HUMIDITY 
PROTECTION2 control will activate airflow PRESET 3 
when the following conditions are met:
-  HUMIDITY PROTECTION2 control is permitted;
-  For MANUAL mode setting ON;
-  For AUTO mode setting AUTO ONLY or ON.
-  The relative humidity of the extract air exceeds 

75%;

-  The unit has not been turned off within last two 

minutes.

This functions is set to AUTO ONLY by default.

The HUMIDITY PROTECTION2 is based on a central 
sensor. Using a local humidity sensor for the wet 
rooms where the humidity is produced, is always 
faster and more reliable.

Humidity protection works for high humidity only. It 
doesn’t protect the building from low humidity.

This menu is only visible when the advanced mode is active.

Содержание ComfoAir Q

Страница 1: ...Cooling Fresh Air Clean Air Heating Ventilation system Zehnder ComfoAir Q Manual for the user ComfoAir Q TR ComfoAir Q ST...

Страница 2: ...age of this document Use of the unit The unit may only be used when it is properly installed according to the instructions and guidelines in the installer manual of the unit The unit can be used by ch...

Страница 3: ...tting the comfort options 15 3 5 1 Temperature profile 15 3 5 2 Scheduler 16 3 5 3 Bypass heat recovery for a specific duration 18 3 5 4 Stop ComfoCool Q for a specific duration 18 3 6 Checking the st...

Страница 4: ...g the internal filters 28 5 5 1 View filter status 28 5 5 2 Postponing filter warning 28 5 5 3 Replacement instruction 29 6 Malfunctions 30 6 1 Airflow is not as expected 31 6 2 Condensation on the ou...

Страница 5: ...to the unit can occur Do not open the casing The installer makes sure that all parts that can cause personal injury are behind the casing The installation commissioning and maintenance must be carried...

Страница 6: ...receiver Zehnder ComfoSwitch C 55 For basic remote manual and automatic control of the unit The automatic control is based on the unit settings This is a wired control Zehnder ComfoSwitch C 67 For ba...

Страница 7: ...KNX connectivity options Zehnder ComfoConnect LAN C Provides LAN connectivity options for remote control with the ComfoControl app Zehnder ComfoCool Q600 Decreases the temperature and pre conditions...

Страница 8: ...light On The unit is operating correctly Off The unit has no power or the display is in use Slowly flashing every second Warning Change filters or SERVICE MODE active Rapidly flashing four times a se...

Страница 9: ...d control G Current ventilation mode AUTO the airflow is set by the scheduler MANUAL the airflow is set by the user H Temporary override of the SCHEDULER VENTILATION I Current fan mode no icon both fa...

Страница 10: ...FROST PREHEATER3 SEASON DETECTION2 BYPASS RF SETTINGS2 8 COMFOCOOL3 ANALOG INPUT3 SUBSOIL HEAT EXCH 3 COMFOCOOL3 SEASON DETECTION FANS ENERGY INSTALLER DEFAULT2 TASK MENU 1 This menu is only visible...

Страница 11: ...Access the unit display To save energy the unit display screen will be off most of the time The display will automatically turn off after 15 minutes of no activity The following actions will make the...

Страница 12: ...hapter How to navigate through the unit menu 2 Navigate to AUTO MANUAL 3 Navigate to MANUAL 4 Select the desired airflow with the up and down button A away if the house will be empty 1 low if you want...

Страница 13: ...the chapter How to navigate through the unit menu 2 Navigate to VENTILATION 3 Navigate to SUPPLY ONLY if you would like to stop extracting air EXTRACT ONLY if you would like to stop supplying air if a...

Страница 14: ...you will come home to a comfortable and fresh house e g after a long holiday 1 Navigate to TASK MENU as instructed in the chapter How to navigate through the unit menu 2 Navigate to AWAY 3 Navigate t...

Страница 15: ...unit are set to provide a comfort level desired by the average person 3 5 1 Temperature profile The amount of heat recovery is controlled automatically based on the set temperature profile The effect...

Страница 16: ...ram is the leading program and overrules any longer program If both overlapping programs have an equally long period the program with the highest airflow PRESET will be the leading program When no sch...

Страница 17: ...program will end the next day 10 Select CONFIRM after each number 11 Navigate to your desired preset for the defined timeslot AWAY airflow if the house will be empty 1 airflow if you want low ventilat...

Страница 18: ...IVATED if you would like to maximise the heat recovery as much of the heat from the extracted air will be transferred back to the supply air as possible 4 Select the desired duration with the up and d...

Страница 19: ...BYPASS The unit is running at a lower airflow rate than normal due to a request from the bypass See chapter Heat recovery control bypass for a specific duration for more information about the bypass c...

Страница 20: ...fans PREHEATER view the current electrical consumption of the preheater YEAR TO DATE view the energy consumption of the fans since the beginning of the year TOTAL view the total energy consumption of...

Страница 21: ...Navigate to the desired language 3 9 Setting the unit display brightness 1 Navigate to BASIC OPTIONS as instructed in the chapter How to navigate through the unit menu 2 Navigate to BRIGHTNESS 3 Navi...

Страница 22: ...all settings in the TASK MENU excluding the set scheduler s will be returned to the default factory settings RESET INCL SCHEDULE You can find this menu under RESET ALL TASKS When this menu is activat...

Страница 23: ...etting ON For AUTO mode setting AUTO ONLY or ON It is cooling season The indoor temperature is significantly higher than the temperature outside The bypass control is in AUTO mode The ComfoCool is tur...

Страница 24: ...it is equipped with a function to detect the current season The detection is based on the RMOT5 In the menu SEASON DETECTION2 you can set the RMOT5 temperature on which the HEATING SEASON2 and COOLING...

Страница 25: ...d manufactured for use in balanced ventilation systems incorporating Zehnder heat recovery systems Any other application is seen as inappropriate use and can result in damage to the unit or personal i...

Страница 26: ...to be compromised Keep a clearance in front of the unit of at least 1m This room is needed to carry out the maintenance activities 1m 5 1 Fill the condensation drain The condensation drain is connecte...

Страница 27: ...ce 3 Remove the filter behind the valve if present 4 Clean the valve with a soft brush vacuum cleaner or soapy water 5 Rinse the valve and then dry 6 Replace the filter behind the valve if present 7 P...

Страница 28: ...Navigate to FILTERS as instructed in the chapter How to navigate through the unit menu 2 Navigate to FILTER STATUS 5 5 2 Postponing filter warning When the unit is displaying the message EXPECT FILTER...

Страница 29: ...new supply filter with the arrow pointing up into the unit Insert new extract filter with the arrow pointing up into the unit Insert filter caps Place the click connection of the filter caps on top of...

Страница 30: ...ow to navigate through the unit menu 2 Wait for 2 minutes If the error reoccurs 3 Navigate to STATUS 4 Navigate to ERRORS 5 Write down all the malfunction code s Select NEXT to view more errors 6 Sele...

Страница 31: ...unit 6 2 Condensation on the outside of the unit and or air ducts When the unit is installed in an area with a higher average humidity such as bathroom or wc the probability of condensation on the out...

Страница 32: ...type Measured by Unit type Return Room Position Required m3 h Tested m3 h Type valve Settings valve Kitchen Bathroom Toilet Total Supply Room Position Required m3 h Tested m3 h Type valve Settings va...

Страница 33: ...tivity Y1 Y2 Y3 Y4 Y5 Y6 Y7 Replace the filters Clean the valves Clean the grilles Clean the valves and grilles Clean the operating device Fill the condensation drain of the domestic waste water syste...

Страница 34: ...Y9 Y10 Y11 Y12 Y13 Y14 Replace the filters Clean the valves Clean the grilles Clean the valves and grilles Clean the operating device Fill the condensation drain of the domestic waste water system Ins...

Страница 35: ...EN 35 Data Activity Initials...

Страница 36: ...hland GmbH Sales International Almweg 34 77933 Lahr Germany T 49 78 21 586 392 F 49 78 21 586 406 sales international zehndergroup com www international zehnder systems com ZGNL_Manual_40015974 V0118...

Отзывы: