3.2.3  STATUS (read only)

Menu item

Function

CURRENT ERRORS

To view the codes of the current errors.

UNIT

To view the information about the unit.

  HRU TYPE: view the type name of the unit;

  FIRMWARE VERSION: view the firmware version of the unit;

  SERIAL NUMBER: view the serial number of the main board in the unit.

SCHEDULER

To view the scheduler step in which the unit is currently running.

  VENTILATION: view which step of the ventilation scheduler is in operation;

  COMFOCOOL3: view which step of the ComfoCool Q600 scheduler is in operation.

TEMP. AND HUMIDITY

To view the current temperature and humidity of the airflows.

  EXTRACT AIR TEMP.: view the current temperature of the extract airflow;

  EXTRACT AIR HUM.: view the current humidity level of the extract airflow;

  EXHAUST AIR TEMP.: view the current temperature of the exhaust airflow;

  EXHAUST AIR HUM.: view the current humidity level of the exhaust airflow;

  OUTDOOR AIR TEMP.: view the current temperature of the outdoor airflow;

  OUTDOOR AIR HUM.: view the current humidity level of the outdoor airflow;

  SUPPLY AIR TEMP.: view the current temperature of the supply airflow;

  SUPPLY AIR HUM.: view the current humidity level of the supply airflow.

BYPASS STATE

To view the current state of the heat recovery control (bypass). 

  The percentage of bypassed air is shown.

FROST UNBALANCE

To view the current state of airflow unbalance caused by the frost protection function.

  The percentage of supply air reduction is shown.

FROST PREHEATER3

To view the current state of the preheater caused by the frost protection function.

  The current power of the preheater is shown.

POSTHEATER3

To view the current state of the post-heater.

  The percentage of the post-heater control is shown.

ANALOG INPUT3

To view the current state of the analog input(s)

  0-10V 13: view the voltage level of the first analog input.

  0-10V 23: view the voltage level of the second analog input.

  0-10V 33: view the voltage level of the third analog input.

  0-10V 43: view the voltage level of the fourth analog input.

SUBSOIL HEAT EXCH.3

To view the current state of the regulated subsoil heat exchanger (e.g. ComfoFond-L Q).

  STATE: view the current state of the regulated subsoil heat exchanger pump;

  OUTDOOR AIR TEMP.: view the current outdoor air temperature;

  GROUND TEMPERATURE: view the current temperature of the regulated subsoil heat exchanger 

brine liquid.

COMFOCOOL3

To view the current state of the ComfoCool Q600.

  STATE: view the current ComfoCool Q600 mode and the current ComfoCool Q600 supply air 

temperature;

  CONDENSER TEMP: view the current condenser temperature.

SEASON DETECTION 

To view the current season detection state.

  SEASON: view the current season mode;

  LIMIT RMOT HEAT: view the set RMOT4 below which the (central) heating system is normally active;

  LIMIT RMOT COOL: view the set RMOT4 above which the (central) cooling system is normally 

active;

  CURRENT RMOT: view the current RMOT4.

FANS

To view the current state of the fans

SUPPLY FAN

  FAN SPEED: view the current speed of the fan.

  FAN DUTY: view the current duty of the fan.

  FLOW: view the current airflow of the fan.

EXTRACT FAN

  FAN SPEED: view the current speed of the fan.

  FAN DUTY: view the current duty of the fan.

  FLOW: view the current airflow of the fan.

ENERGY

To view the energy consumption and saved energy.

POWER CONSUMPTION

  VENTILATION: view the current electrical consumption of the fans.

  PREHEATER: view the current electrical consumption of the preheater.

  YEAR TO DATE: view the energy consumption of the fans since the beginning of the year.

  TOTAL: view the total energy consumption of the fans since the moment of commissioning.

AVOIDED HEATING

  ACTUAL POWER: view the current avoided heating power.

  YEAR TO DATE: view the avoided heating energy since the beginning of the year.

  TOTAL: view the avoided heating energy since the moment of commissioning.

AVOIDED COOLING

  ACTUAL POWER: view the current avoided cooling power.

  YEAR TO DATE: view the avoided cooling energy since the beginning of the year.

  TOTAL: view the avoided cooling energy since the moment of commissioning. .

TOTAL SAVINGS

  YEAR TO DATE: to view the total energy savings since the beginning of the year.  

  TOTAL: to view the total energy savings since the moment of commissioning.

3 This menu is only visible when the accessory is connected to the unit.

4 RMOT = running mean outdoor temperature (average temperature over past five days).

Содержание ComfoAir Q 350 ST

Страница 1: ...Cooling Fresh Air Clean Air Heating Ventilation system Zehnder ComfoAir Q User manual ...

Страница 2: ...f this document Use of the unit The unit may only be used when it is properly installed according to the instructions and guidelines in the installer manual of the unit The unit can be used by children aged from 8 years and above persons with reduced physical capabilities persons with reduced sensory capabilities persons with reduced mental capabilities persons with lack of experience and knowledg...

Страница 3: ... Set the airflow to a minimum for the period of your absence PRESET A 11 3 1 8 Set the temperature profile 11 3 1 9 Set a schedule 12 3 1 10 Manually set the heat recovery control bypass for a specific duration 12 3 1 11 Stop the ComfoCool Q600 for a specific duration 12 3 2 Menu structure 13 3 2 1 RESET ERROR1 14 3 2 2 TASK MENU 14 3 2 3 STATUS read only 15 3 2 4 FILTERS 16 3 2 5 BASIC OPTIONS 16...

Страница 4: ...4 EN ...

Страница 5: ... regulations warnings comments and instructions in this document are not obeyed personal injury or damage to the unit can occur After installation all parts that can cause personal injury are secured behind the casing You need tools to open the casing The installation commissioning and maintenance must be carried out by a certified engineer unless the instructions state otherwise A non certified e...

Страница 6: ...his is a wired control with a wireless receiver Zehnder ComfoSwitch C 67 For basic remote manual and automatic control of the unit The automatic control is based on the unit settings This is a wired control Zehnder Control App For remote manual and automatic control of the unit with a smartphone or tablet The automatic control is based on the adjustable scheduler This is a controller connected to ...

Страница 7: ...ptions Zehnder ComfoConnect KNX C Provide KNX connectivity options Zehnder ComfoConnect LAN C Provide LAN connectivity options for remote control Standby switch Stop the unit remotely This ancillary is connected to the Option Box Error contact Remotely check the error status of the unit This ancillary is connected to the Option Box External filter Filter pollen from the outdoor air Post heater Inc...

Страница 8: ...te the unit 2 4 Overview of the display AUTO sensor SHIFT MENU Tu 14 02 A B C E D Position Part A Status indicator LED light B Universal button The function depends on the current text on the display C Up button to Increase fan speed Increase value Select the previous item D Down button to Decrease fan speed Decrease value Select the next item E Universal button The function depends on the current...

Страница 9: ... sensor can not overrule the current set airflow G Current ventilation mode AUTO the airflow is set by the scheduler MANUAL the airflow is set by the user H Temporary override of the SCHEDULER VENTILATION I Current fan mode no icon both fans are in operation BALANCE extract fan is not in operation SUPPLY ONLY supply fan is not in operation EXTRACT ONLY both fans are not in operation SERVICE MODE P...

Страница 10: ...nt airflow volume in m3 h or l s B Current supply fan mode no icon fan is not in operation fan is in operation C Current outdoor air temperature in C or F Only visible when the supply fan is active D Current supply air temperature C or F Only visible when the supply fan is active E Current extract fan mode no icon fan is not in operation fan is in operation 2 4 3 Overview of the visual signals of ...

Страница 11: ...urs the unit will automatically switch back to AUTO mode To set a permanent airflow 1 Navigate to TASK MENU 2 Navigate to AUTO MANUAL 3 Navigate to MANUAL 4 Select the desired airflow with the up and down button 5 Select CONFIRM 6 Select CONFIRM Stop the MANUAL mode 1 Repeat step 1 and 2 2 Navigate to AUTO 3 1 5 Set the airflow to a maximum BOOST for a specific duration 1 Navigate to TASK MENU 2 N...

Страница 12: ...th the up and down button 10 Select CONFIRM after each number 11 Select navigate to your desired setting 3 1 10 Manually set the heat recovery control bypass for a specific duration 1 Navigate to TASK MENU 2 Navigate to BYPASS 3 Navigate to OPEN if you would like to minimise the heat recovery control outdoor air is supplied directly into the dwelling DISABLE if you would like to maximise the heat ...

Страница 13: ... PROFILE FROST UNBALANCE UNITS2 SCHEDULER FROST PREHEATER3 SEASON DETECTION2 BYPASS POSTHEATER3 RF SETTINGS2 7 COMFOCOOL3 ANALOG INPUT3 SUBSOIL HEAT EXCH 3 COMFOCOOL3 SEASON DETECTION FANS ENERGY INSTALLER DEFAULT2 TASK MENU 1 This menu is only visible when errors occur 2 This menu is only visible when the advanced mode is active 3 This menu is only visible when the accessory is connected to the u...

Страница 14: ...ependent in case the installation is equipped with one or more of the options that follow active cooling e g ComfoCool Q600 heating devices e g pre heater and or post heater a regulated subsoil heat exchanger e g ComfoFond L Q SCHEDULER To set the settings automatically based on the set schedule This function is stopped in the permanent MANUAL mode VENTILATION Default PRESET 2 VIEW EDIT view or se...

Страница 15: ...subsoil heat exchanger e g ComfoFond L Q STATE view the current state of the regulated subsoil heat exchanger pump OUTDOOR AIR TEMP view the current outdoor air temperature GROUND TEMPERATURE view the current temperature of the regulated subsoil heat exchanger brine liquid COMFOCOOL3 To view the current state of the ComfoCool Q600 STATE view the current ComfoCool Q600 mode and the current ComfoCoo...

Страница 16: ...foCool Q600 pre heater post heater ON the unit will increase the airflow in the AUTO mode and MANUAL mode if requested by the built in sensors AUTO ONLY the unit will only increase the airflow in the AUTO mode if requested by the built in sensors OFF the unit will ignore the request to increase the airflow by the built in sensors default setting HUMIDITY COMFORT2 Increase the airflow automatically...

Страница 17: ...nd save the current RMOT4 as the heating limit5 COOLING SEASON2 Prevent the unit from counteracting the effect of the central cooling system COOLING LIMIT RMOT4 set the cooling limit6 RMOT4 Default 20 C STARTS NOW start the cooling season and save the current RMOT4 as the cooling limit6 RF SETTINGS2 7 To set the settings of the RF sensor s RF SENSOR PRIORITY2 7 ON the unit will translate the signa...

Страница 18: ...nd manufactured for use in balanced ventilation systems incorporating Zehnder heat recovery systems Any other application is seen as inappropriate use and can result in damage to the unit or personal injury for which the manufacturer cannot be held liable The manufacturer is not liable for any damage originating from Non compliance with the safety operating and maintenance instructions in this doc...

Страница 19: ...room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tightness m h 11 AEC in kW...

Страница 20: ...isplay of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tigh...

Страница 21: ...room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tightness m h 11 AEC in kW...

Страница 22: ...isplay of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tigh...

Страница 23: ...troller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tightness m h 11 AEC in kWh electr...

Страница 24: ...f the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Warning on the display of the unit or room controller Internet address for assembly and disassembly instructions www zehnder co uk www zehnder co uk www zehnder co uk www zehnder co uk Airflow sensitivity to pressure variations 10 Indoor outdoor air tightness m ...

Страница 25: ...s more information about the indication on filter replacement Replace the filters at least every six months This will insure a comfortable and healthy air quality and will protect the unit from pollution When you need to replace the filters 1 Order new filters Contact the installer of the unit for providing the correct filters or order online at www epicair co uk Filter set Order number G4 G4 1x 1...

Страница 26: ...at least every six months 1 Keep hold of the grille on its outer edge and pull it completely out of the wall or ceiling if not screwed down 2 Clean the grille with a soft brush or vacuum cleaner 3 Clean the filter behind the grille if present with soft brush or vacuum cleaner Do not remove the foam behind the grille if present as it would negatively influence the system performance 4 Place the gri...

Страница 27: ...th mould When the unit is installed in an area with a higher average humidity such as bathroom or wc the probability of condensation on the outside of the unit is high This is almost the same as condensation on a window on which no action is needed In the event of a filter malfunction replace the filter as described in the maintenance chapter In the event of all other malfunctions follow these ste...

Страница 28: ...ese should be detailed here Description of installed controls e g timer central control humidistat PIR etc Location of document override controls Signature Number if applicable Date of Installation completion 2 2 Installation Engineer s Details Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code Signature Competent Person Scheme Registration number if applicable Date o...

Страница 29: ... protection packaging been removed including background ventilators such that system is fully functional Yes No For ducted systems has the ductwork installation been installed in such manner that air resistance and leakage is kept to a minimum Yes No Are the correct number and size of background ventilators provided that satisfy ADF Yes No Has the entire system been installed such that there is su...

Страница 30: ...e 5 1b in ADF Kitchen Bathroom En Suite Utility Other Other Other 3 4 Air Flow Measurements supply system 4 only Room reference location of terminals Measured Air Flow High Rate l s Design Air Flow High Rate l s Refer to Table 5 1b ADF Measured Air Flow Low Rate l s Design Air Flow Low Rate l s Refer to Table 5 1b in ADF Living Room 1 Living Room 2 Dining Room Bedroom 1 Bedroom 2 Bedroom 3 Bedroom...

Страница 31: ...ctivity Y1 Y2 Y3 Y4 Y5 Y6 Y7 Replace the filters Clean the valves and grilles Clean the operating device Fill the condensation drain of the domestic waste water system Inspect and clean the casing of the unit Inspect and clean the heat exchanger Inspect and clean the fans Inspect and clean the modulating by pass Inspect and clean the pre heater Inspect and clean the condensation drain of the unit ...

Страница 32: ... Y9 Y10 Y11 Y12 Y13 Y14 Replace the filters Clean the valves and grilles Clean the operating device Fill the condensation drain of the domestic waste water system Inspect and clean the casing of the unit Inspect and clean the heat exchanger Inspect and clean the fans Inspect and clean the modulating by pass Inspect and clean the pre heater Inspect and clean the condensation drain of the unit Inspe...

Страница 33: ...EN 33 Data Activity Initials ...