EN - 10
2.7.2 P menus for the user
Menu P1
Status of programmes
Status
Sub-
menu
Description
Activated
P11
Is menu 21 currently active?
Yes (1) / No (0)
P12
Is menu 22 currently active?
Yes (1) / No (0)
P13
Is menu 23 currently active?
Yes (1) / No (0)
P14
Is menu 24 currently active?
Yes (1) / No (0)
P15
Is menu 25 currently active?
Yes (1) / No (0)
P16
Is menu 26 currently active?
Yes (1) / No (0)
Menu P2
Setting time delays
Time delay values
Sub-menu
Description
Minimum
Maxi-
mum
General
Reset
P21
(Optional)
Note:
Only applies to systems
fi tted with a corded switch
and a second switch in the
bathroom.
Delay timer for the bathroom switch (to
switch to high position).
•
'x' minutes after operating the bathroom
switch, the ComfoAir switches to the
HIGH
SETTING
.
- Low voltage input
0 Min.
15 Min.
0 Min.
P22
(Optional)
Note:
Only applies to systems
fi tted with a corded switch
and a second switch in the
bathroom.
Overrun timer for the bathroom switch (to
switch to normal position).
•
'x' minutes after operating the bathroom
switch, the ComfoAir switches back to the
NORMAL
SETTING
.
- Low voltage input
0 Min.
120 Min. 30 Min.
P23
(Optional)
Note:
Only applies to systems
fi tted with a hardwired
3-position switch.
Overrun timer for ventilation position 3 (us-
ing an wired 3-position switch).
•
If ventilation setting 3 (high) is switched
on briefl y (< 3 sec), the ComfoAir will
switch to the
HIGH
SETTING
for 'x' minutes
and then automatically returns to the
NOR
-
MAL
SETTING
.
If any 3-position switch is operated during
this lagging time the ComfoAir will instantly
revert to the ventilation position as set at
that time.
0 Min.
120 Min.
0 Min.
P24
Filter warning
• 'x' weeks after cleaning the fi lters the "
FIL
-
TER
DIRTY
" alert will reappear.
10 weeks 26 weeks
16
weeks
P25
Note:
Only applies to systems fi t-
ted with an RF switch.
Overrun timer for ventilation setting 3 (using
"
").
•
After pressing "
" briefl y (< 2 sec.), the
ComfoAir will switch to the
HIGH
setting for
‘x’ minutes and then automatically returns
to the
NORMAL
setting.
If any 3-position switch is operated during
this lagging time the ComfoAir will instantly
revert to the ventilation position as set at
that time.
1 Min.
20 Min.
10 Min.