7 - EN
Time delay values
sub-menu
description
Minimum Maximum General
reset
P25
Note:
Only applies to systems fit-
ted with an rF switch.
Overrun timer for ventilation setting 3 (us-
ing "
").
• After pressing "
" briefly (< 2 sec.),
the ComfoAir will switch to the
high
set-
ting for ‘x’ minutes and then automati-
cally returns to the
normal
setting.
If any 3-position switch is operated during
this lagging time the ComfoAir will instant-
ly revert to the ventilation position as set
at that time.
1 Min.
20 Min.
10 Min.
P26
Note:
Only applies to systems fit-
ted with an rF switch.
Overrun timer for ventilation setting 3 " us-
ing
".
• After pressing "
"
continuously
(> 2
sec.), the ComfoAir will switch to the
high
setting for ‘x’ minutes and then au-
tomatically returns to the
normal
setting.
If any 3-position switch is operated during
this lagging time the ComfoAir will instant-
ly revert to the ventilation position as set
at that time.
1 Min.
120 Min.
30 Min.
P27
N/A
0 Min.
120 Min.
30 Min.
Menu P9
¨
Status of programmes (from menu P5 and P6 additional programmes)
status
sub-menu
description
Activated
P90
Open fire programme active?
Yes (1) / No (0)
P91
Bypass Open?
Yes (1) / No (0)
P94
Analogue input (0-10V) active?
Yes (1) / No (0)
P95
Frost protection or Preheater active?
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)