3
For the installer - 35 - EN
A8
Malfunction
Pre-heater becomes too hot
Remove filter caps
and front
Does Pre-heater valve work okay?
(check with P81)
Yes
Check the following:
- fan settings (too low?)
- supply diffusers (not open enough?)
- supply ducting (blockages?)
No
See A5 / A6 malfunctions from
‘Activate self-test’
A7
Malfunction
Pre-heater does not heat (sufficiently)
Disconnect the power
Remove filter caps
and front
Unplug Pre-heater from the PCB
Is resistance of
Pre-heater
plug > 300 ohms?
Yes
Remove Pre-heater
Is resistance of
Pre-heater
cable infinite?
Yes
Fuse defective
Replace cable
No
Is resistance
of T1 okay?
No
Yes
Replace T1
temperature sensor
Replace PCB
No
Check resistance of cable
and check connections
to Pre-heater
ATTENTION!
Risk of electrocution:
do not touch the PCB
or the pre-heater.
ATTENTION!
Risk of electrocution:
do not touch the PCB
or the pre-heater.