10 - EN
3 Commissioning
3.1 Programming air specifications
0
50
100
150
200
250
300
350
400
0
50
100
150
200
250
300
p
st
[Pa
]
Qv [m
3
/h]
100%
40%
30%
15%
90%
80%
70%
60%
50%
The unit has been programmed with two sets of
standard ventilation settings. These sets can be
chosen in menu P56. When a general reset is given
the menu will be set to the HL ventilation settings.
From the factory the unit will be delivered with the nL
ventilation settings.
In menu P3 the pre-programmed ventilation settings
can be altered. The supply fan and the exhaust
fan can be set independently for all 4 ventilation
settings.
The absent setting cannot be chosen with a normal
3 position switch. For this the unit would need a
ComfoSense.
Default settings air volume
nL
HL
Absent Setting
15%
15%
Low Setting
35%
40%
Medium Setting
50%
70%
High Setting
70%
90%
Follow this procedure to determine which settings the installation needs:
1
2
Example valve
3
Close all windows and doors.
When the property is being
occupied make sure the
air ducts are clean before
programming the air
specifications.
Open all valves and grilles fully.
Set the unit in programming mode.
■
Display:
Press simultaneously for at least 3
seconds on
and
until
“Inr” appears on the display;
■
ComfoSense:
Activate INIT menu.
In programming mode, the
bypass valve is always closed.
After 30 minutes, the unit
automatically terminates the
programming mode.