Read carefully the instructions before installing this unit. Verify the tech-
nical characteristics of the motor in order to assure the compatibility with
the device.
DESCRIPTION (diagram A)
ZP Control 01 Basic
is an electronic pressure switch with integrated digital
ma-nometer. It manages the start and stop of a single-phase pump up
to 2.2kW (3 HP). Cut-in and cut-out pressures are easily adjustable
through the users control panel.
Wiring is analogous to the traditional electromechanical switch.
It can operate as a diff erential pressure switch and as reverse pressure
switch.
CLASSIFICATION AND TYPE
According to IEC 60730-1 and EN 60730-1 this unit is a control sensor
device, electronic, independent assembly, programming type A with action
type 1B (microdisconnection). Operating value: I <20% I learned. Pollution
degree 2 (clean environment). Rated impulse voltage: cat II / 2500V. Tem-
peratures for ball test: enclousure (75) and PCB (125).
OPERATING CHARACTERISTICS (diagram C)
• Adjustable cut-in and cut-out pressures.
• Integrated digital pressure gauge with bar and psi indication.
• Inner pressure transmitter.
• Dry-run protection:
• Through minimum adjusted height for
ZP Control 01 Basic
.
• ART Function (Automatic Reset Test). When the device has stopped
the pump by the intervention of the dry-running protection system,
the ART tries, with scheduled basis, to re-start the pump in order to
restore the water supply. See “ART. Automatic reset function“. Must
be activated in the step 6 of the ADVANCED MENU (Ar1).
• Fast cycling: when the hydropneumatic tank has lost too much air
and,
consequently, frequent start-stop cycles are produced this alarm is
activated and is delayed the start of the pump. Must be activated in
the step 2 of the BASIC MENU (rc1).
• Manual start push-button (ENTER).
• Control panel with 3-digit display, LED indicator lights and push-
buttons.
• Available settings:
• Stand-by mode.
• Minimum period between fast cycles.
• Start and stop delay.
TECHNICAL CHARACTERISTICS
0,37-2,2 kW
~1 x 110-230 V
0,8 MPa
50/60Hz
16 A
IP55
50ºC
60ºC
0,5
÷
7 bar
1÷8 bar
7,5 bar
0,5÷1,5 bar
3/4 bar
G 1/4” Female
• Rated motor power:
• Power supply:
• Pessure max.
• Frequency:
• Max. current:
• Protection degree:
• Max water Temperature:
• Max environment Temperature:
• Cut-in range (start pressure)
• Cut-ot range (stop pressure)
• Max. diff erential
• Minimum diff erential (adjustable)
• Factory setting (start/stop)
• Hydraulic inlet
• Net weight (without cables)
0,3 kg
HYDRAULIC INSTALLATION
ZP Control 01 Basic
equipment must be threaded to a fi tting G1/4”
male at the pump´s outlet.
Before connecting the
ZP Control 01 Basic
verify that the hydraulic system
is properly installed, especially if the hydropneumatic tank is pressurized.
ELECTRIC CONNECTION (diagram B)
The electric connection must be performed by qualifi ed personal in
compliance with regulation of each country.
Before doing manipulations inside the device, it must be disconnected
from the electric supply.
Wrong connection could spoil the electronic circuit.
The manufacturer declines all responsability in damages caused by
wrong connections.
Check if power supply is between 115-230V.
If you have purchased the unit without cables follow diagram B:
• Use cables type H07RN-F 3G1 or 3G1,5 with section enough to the
power installed.
• Do the pump connection U, V and .
• Do the power supply connection L1, N and .
• The earth conductor must be longer than the others. It will be the fi rst
one to be mounted during the assembly and the last one to be dis-
connected during the dismantling.
The earth conductors connec-
tions are compulsory!
CONTROL PANEL (diagram C)
The meanings of the diff erent control panel elements are summarized on
the following tables, where:
• O means lit LED light.
• ( ( O ) ) means slow-fl ashing.
• (((O))) means fast-fl ashing.
DISPLAY
ACTION
OPERATION MODE
Is showed on screen instant
a
neous pressure or instanta-
neous current consumption
ADJUSTMENT MODE
Is displayed on screen the adjusted start pressure
blinking.
Is displayed on screen the adjusted stop pressure blin-
king.
ALARM MODE
Is displayed the alarm code
STAND-BY MODE
Are displayed 3 fl ashing dots
BASIC CONFIGURA-
TION MODE
Is displayed the sequence of basic confi guration para-
meters
ADVANCED CONFI-
GURATION MODE
Is displayed the sequence of advanced confi guration
parameters
LEDS
STATE
MEANING
bar
O
It indicates the instantaneous pressure in bar
( ( O ) )
It indicates the instantaneous pressure in bar +
pump operating
psi
O
It indicates the instantaneous pressure in psi
( ( O ) )
It indicates the instantaneous pressure in psi +
pump operating
A
(only SW2)
O
It indicates the instantaneous current consumption
in Ampere units
( ( O ) )
Pump ON
START
O
Is displayed the start pressure
( ( O ) )
Adjusting start pressure
STOP
O
Is displayed the stop pressure
( ( O ) )
Adjusting stop pressure
O
Ratifi ed dry-running or overload alarms
( ( O ) )
Dry-running alarm performing ART or overload
alarm preforming any of the 4 restore attempts
(((O)))
Fast-cycling alarm
Adjustment of ZP Control 01 Basic