56 / 103
Identification: MD-AL-GI-00
Rev. 1.1 of 12/03/2021 - Application: GID
User’s Manual 1PH 1100TL-3300TL-V3
Rev. 1.1 12/03/2021
18.
P(f) Setting
Select “21. Set P(f)” and long press the key to enter the relative menu, from which you can change the active
power according to the grid frequency required by the local regulations. This function may be required by
various regulations for grid-connected inverters. Short press the key to change the selected value and long
press the key to go to the next digit; it will be possible to set the time delay expressed in seconds (*.***s)
before the modified P active power will intervene.
19.
Q(v) Setting
Select “22. Set Q(V)” and long press the key to enter the relative menu, from which you can change the
reactive power according to the grid voltage required by the local regulations. This function may be required
by various regulations for grid-connected inverters. Short press the key to change the selected value and
long press the key to go to the next digit; it will be possible to set the time delay expressed in seconds
(*.***s) before the modified Q reactive power will intervene.
20.
Control 81.S1
Select “23. 81.S1Check” and long press the key to enter the relative menu, from which it will be possible to
enable the frequency restriction thresholds required in special cases by the local regulations. Short press the
key to set the option “1. Enable 81.S1” and “2. Disable 81.S1” and select it by long pressing the key. The
display will show “OK” if the setting is successful.