Figure 22 – Removing the DC connector
4.4.
Connecting the AC output power cables
Connect the inverter to the AC power distribution network or power grid using AC power cables.
Do not use the same AC circuit breaker for multiple inverters
.
Do not install loads between the inverter and the AC circuit breaker
.
The switch used as a disconnection device should always be operational and ready
to operate.
Warning
Context
The AC power cables used for the inverter must be three-pole outdoor cables. For easier installation, use
flexible cables. The table lists the recommended specifications for cables and circuit breakers.
Type
1100TL-V3
1600TL-V3
2200TL-V3
2700TL-V3
3000TL-V3
3300TL-V3
Cable (mm
2
)
>4
>4
>4
>6
>6
>6
Switch
16A/400V
16A/400V
25A/400V
25A/400V
25A/400V
25A/400V
Table 2 – Recommended specifications for AC output cables