3.6 CPR Crankcase Pressure
Regulation Valve
Cooling Circuit
(i)
i Clean pipe ends with a special
brush and flow with dry nitrogen.
CAUTION
!
Never flow with
normal air, it contains too much
humidity.
(j)
Braze new CPR valve in position.
CAUTION
!
Wrap CPR valve in a
wet rag, which must be warmer than
ambient avoiding moisture
condensation.
(k)
Reinstall evaporator service ports
valves.
(s)
CAUTION
!
Lubricate valve
gaskets before.
(l)
Vacuum contaminated part of cooling circuit from LP service port.
(m)
Test installation for leaks with a vacuum gauge.
(n)
Reinstall valve support brackets.
(o)
Charge unit with refrigerant
3.2.4
Section.
Regulate CPR valve
3.6.1
Section.
Содержание un0 010
Страница 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Страница 4: ......
Страница 15: ......
Страница 16: ......
Страница 17: ...Section1 Generalinformation...
Страница 19: ......
Страница 30: ......
Страница 31: ...Section2 Descriptionoftheunit...
Страница 33: ......
Страница 37: ...26 Description of the unit 2 1 Condensing unit Under Mount Discharge line Suction line Heat defrost line...
Страница 45: ...34 Description of the unit 2 2 Evaporating section...
Страница 46: ......
Страница 47: ...Section3 CoolingCircuit...
Страница 94: ......
Страница 95: ...Section4 DieselEngine...
Страница 97: ......
Страница 98: ...87 4 1 Belts Diesel Engine 4 Diesel Engine 4 1 Belts Individual Protection Devices Googles Gloves Proper tools...
Страница 130: ......
Страница 131: ...Section5 ElectronicsandWirings...
Страница 135: ......
Страница 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Страница 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Страница 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Страница 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Страница 178: ......
Страница 179: ...Section6 Alarms Troubleshooting...
Страница 181: ......
Страница 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Страница 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Страница 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Страница 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Страница 187: ...176 Alarms Troubleshooting 6 1 StandardAlarms A14 Net compressor high temperature A15 Low Battery...
Страница 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Страница 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Страница 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Страница 193: ...182 Alarms Troubleshooting 6 3 Troubleshooting 6 3 Troubleshooting Condenser fan is not running...
Страница 194: ...183 6 3 Troubleshooting Alarms Troubleshooting Evaporator fan is not running F20 Fuse blows often...
Страница 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Страница 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Страница 197: ......
Страница 198: ......
Страница 199: ...Annex1 Parameters...
Страница 201: ......
Страница 208: ......
Страница 209: ......