RELAY1 / RELAY 2 COMMAND

RELAY1

 <ON/OFF/MEM> <mode> <t1> RING <y>

RELAY2

 <ON/OFF/MEM> <mode> <t2> RING <y>

<ON/OFF/MEM>

  The parameter defines the output status OUT1/OUT2 after switching on power supply from the mains:

ON 

Output switched on.

OFF  Output switched off.

MEM  GRM-10 remembers the output status - when the power supply is switched off and then switched on again, 

the output has the same status as it was before the power supply switch off. The parameter is not adjusted for 

the TIME mode..

<mode>

  A parameter that defines the operating mode of OUT1/OUT2 outputs - it is default for CLIP control.

ONOFF  Bistable mode (Switch on / switch off).

TIME  Time mode.

<t1>/<t2>

  A parameter that defines default times [s] for the time mode - possible value from 1 to 3600

RING

 A keyword defining the number of ring signals to control CLIP.

<y>

 A parameter defining the number of rings to control CLIP. The parameter is adjusted in the range of 2 to 12.

If the RING keyword and <y> parameter is not adjusted, the control is carried out only by sending text messages.

OUT1/OUT2 outputs are independently configurable.

Examples of commands:

Command

Description

RELAY1 ON ONOFF RING 3

OUT1 output is switched on, bistable mode, adjustment after three rings.

RELAY1 MEM ONOFF RING 2

OUT1 output in the status before power supply switch off, bistable mode, acti-

vation after two rings

RELAY1 OFF TIME 60 RING 4

OUT1 output is switched off, time mode, time 60 seconds, adjustment after  

4 rings

RELAY2 OFF ONOFF

OUT2 output is switched off, bistable mode, control only by means of text mes-

sage

RELAY2 ON TIME 10 RING 2

OUT2 output is switched on, time mode, time 10 seconds, adjustment after  

2 rings

GATE COMMAND (GATE MODE)

In the gate mode the settings are as follow:

OUT1 - it cooperates with the existing gate controller that controls the gateway.

OUT2 - it cooperates with the electric latch opening the entry gate to the possession.

The number of telephones authorized to control in the gate mode by means of a ring (CLIP) are adjusted in the CONFIG configuration 

mode (up to 6 numbers) or by means of:

●  the ADD NUM command in the configuration mode,

●  the PC application in the Telephones section / CLIP (up to 500 numbers) in the configuration mode.

GATE

 <TIME 1> <TIME2> 

RING

 <y> 

AUTO

 <TIME3>

<TIME 1>  A parameter that defines the default time [s] of the OUT1 output - configurable in the range of 0 to 10. OUT1 task is to generate 

a pulse to the gateway controller. If this parameter is set to “0”, then OUT1 output is inactive.

<TIME 2>  A parameter that defines the default time [s] of the OUT2 output - configurable from 0 to 360. The OUT2 output task is to pro-

vide voltage supply to the electric latch. If this parameter is set to “0”, then the OUT2 output is inactive.

RING

 A keyword that defines the number of rings to control outputs in the gate mode by means of a CLIP.

<y>  A parameter that defines the number of rings to control outputs in the gate mode by means of a CLIP. This parameter is con-

figured in the range of 2 to 6. If it is not set, the control is carried out only by means of text messages.

AUTO

  A keyword to configure the AUTO mode. In the AUTO mode, after <TIME 3> finishes a gate  

controller’s pulse is au-

tomatically generated for a defined <TIME1> time. This impulse is to automatically close the door. If the AUTO mode is ac-

tivated, the gate remains open till the GATE command is activated, till the next “CLIP’a”, till the next pulse in IN1 input or till 

another pressing of the PK1 push-button.

<TIME3>  A parameter that defines the time [s] during which the gate remains open. The time is measured after <TIME1> finishes. It is 

configured in the range from 1 to 600. While adjusting <TIME3> it is necessary to take into consideration the time taken to 

open the gate..

IN1/IN2 inputs are not configurated in the gate mode. The inputs have the following default settings:

●  The appearance of a short pulse in the IN1 input results in switching on the OUT1 output for the time <TIME1> that is adjusted 

during the gate mode configuration.

●  The appearance of a short pulse in the IN2 input results in switching on the OUT2 output for the time <TIME2> that is adjusted 

during the gate mode configuration..

Examples of commands:

Command

Description

GATE 2 15 RING 2

time1 = 2 s, time2 = 15 s, setting the CLIP after 2 rings

GATE 2 10 RING 2 AUTO 350

time1 = 2 s, time2 = 10 s, setting the CLIP after 2 rings, automatically generat-

ing pulse to close the gate after time3 = 350 s

GATE 2 100

time1 = 2 s, time2 = 100 s, control only by means of tex messages

GATE 0 60

Pulse generation only to open the doorway (latch operation time = 60 s)

GATE 2 0

Pulse generation only to open the gate (pulse time = 2 s)

The GRM-10 connection diagram in the gate mode

INFO COMMAND

INFO

 <+48tel_1> <+48tel_2>,...,<+48tel_n>

tel_1...tel_n  successively entered phone numbers preceded by +48. The text messages will be sent to these numbers. The confirma-

tions refer to the changed output status and occurences on IN1, IN2 inputs.

The maximum of numbers available n = 6.
The confirming text messages are sent only if the ACK parameter is set in the CONFIG command. Sending the INFO command with new 

telephone numbers results in deleting the previous numbers and writing the new ones.
Examples of commands:

Command

Description

INFO +4860248600915257

Text messages will be sent to the following n48602360938, 

+48600915257 confirming the realization of a specified control command or 

occurences on inputs. 

INFO +486024860048600500800

Text messages will be sent to the following n48602360938, 

+48600915257, +48600500800 confirming the realization of a specified control 

command or occurences on inputs. 

MODBUSCONFIG COMMAND

Default MODBUS protocol configuration in GRM-10 device allows for a direct connection with EXTA FREE translator / RS-485 RXM-01 

type. 

GRM-10 device in such a connection is only a MASTER on the MODBUS bus - it receives control text messages and by 

means of RS-485 bus it sends appropriate commands to the RXM-01 device

. A default configuration:

Protocol:

MODBUS RTU 8 bits of data

Parity:

Parity bit + stop bit

Transmission rate:

9600 kbps

Address on the bus:

0x01

MODBUSCONFIG

 <address> <rate> 

PARITY

 <parity options>

<address>  A parameter defining address on the bus: 1...247.

<rate>  A parameter defining transmission rate on the RS-485 bus:

2400 - 2400 kbps,

4800 - 4800 kbps,

9600 - 9600 kbps,

19200 - 19200 kbps

PARITY

 A keyword defining parity options. Selection possibilities:

NO – no parity

ODD – odd test

EVEN – parity test.

Examples of commands:

Command

Description

MODBUSCONFIG 1 9600 PARITY EVEN

Address 0x01, transmission rate 9600kbps, parity test

MODBUSCONFIG 1 2400 PARITY ODD

Address 0x01, transmission rate 2400kbps, odd test

GATE

CONTROLLER

ELECTRIC LATCH 

OF THE DOORWAY

Manual control 

of the gateway

Manual control 

of the doorway

<time3>

*

<time1>

* if the parameter AUTO is set

<time2>

Содержание GRM-10

Страница 1: ...puts with a maximum load capacity of 16 A 250 V AC Two digital inputs allow for a link with the alarm control panels The RS485 in terface in connection with the RXM 01 translator gives a possibility t...

Страница 2: ...he GRM 10 application on the PC 1 After switching off the power supply voltage connect the GRM 10 device to the PC by means of a USB Micro B USB cable and pressing the PK2 push button 2 Start the GRM...

Страница 3: ...pes Remarks MANUAL By means of PK1 PK2 push buttons on the front panel Bistable ON OFF Time TIME Gate GATE Times for TIME and GATE modes are adjusted during con figuration CLIP By calling to the devic...

Страница 4: ...essively entered phone numbers preceded by 48 The text messages will be sent to these numbers The confirma tions refer to the changed output status and occurences on IN1 IN2 inputs The maximum of numb...

Страница 5: ...ng a text message MESSAGE with a defined content X number of an input output 1 input output IN1 OUT1 2 input output IN2 OUT2 tx f the output must be active for a period of time TIME then the parameter...

Страница 6: ...s is 0x01 The address is important for a larger number of RXM 01 operating independently on a single object 3 Following the description of the PC add programme particular push but tons sent by the RXM...

Страница 7: ...X ON Electronics Authorized Distributor Click to view similar products for LED Lighting Fixture Accessories category RZB03 ASM10 ORDBYE115 STR21230V AS223 ORAE1336G ORAE1373 ORWE501 ORWE504 ORWE514...

Отзывы: