Visit our web site at www.z-flex.com

 

SPECIAL STAINLESS STEEL VENTING

 

For use with Category I, II, III, IV appliances 

 

Contact Local Building or Fire Officials about Restrictions and Installation Inspections in your area as well as National codes: USA -

National Fuel Gas Code ANSI-Z223.1/NFPA 54, CANADA -CAN\CGA-B149.1 or .2  Fuel Burning Installation Code  

 

Please  refer  to appliance manufacturers' instructions to determine proper sizing and connection of venting system to appliance, 

including maximum horizontal length, maximum height, and installation clearances (air spaces). The proper operation of the vent 

system and appliance requires parts specified by Z-FLEX with

 

no deletions or

 

substitutions

.  

 

 

 Z-FLEX

 recommends that an experienced professional who works with venting systems on a regular basis perform the installation. 

These instructions are intended as a guide to assist a professional installer.  

    When the

 Z-VENT

 system is installed, the following should be observed: 

 

1.

 A venting system that exits the structure through a sidewall or the like, shall terminate not less than 12 inches (254 mm) above 
the ground (see illustration # 2, page 5). 

 

2.

 The termination of a system shall be located above the snow line in geographical areas where snow accumulates. The termination 

area should be kept clear of snow and ice at all times (see illustration # 2, page 5). 

 

3.

 The vent shall not terminate less than 7 ft. (2.13 m) above a paved sidewalk or driveway. 

 

4.

 The termination shall be 6 ft. (1.8 m) or more from the combustion air intake of any appliance. 

 

5.

 The system shall terminate more than 3 ft. (.91 m) from any other building opening, gas utility meter, service regulator or the 

like. 

 

6.

  Exterior mounted venting systems should be enclosed below the roof line with a chase to limit condensation and protect against 

mechanical  failure.   

Vent  system  must  be  pitched  minimum  ¼”  per  foot  back  to  condensate  drain  within  the 

system.

 

 

NOTES:  

 

A. 

The Z-FLEX SPECIAL STAINLESS VENT SYSTEM is for use only with appliances having a positive vent pressure of 8” of water 

column or less. 

 

B. 

Except for installation in one and two family dwellings, a venting system that extends through any zone above that on which the 

connected appliance is located shall be provided with an enclosure having a fire resistance rating equal to or greater than that of 

the floor or roof assemblies through which it passes. 

 

C.

 Do not place any type of insulation in any required air spaces surrounding the venting system. 

 

D. 

A  termination  must  be  used  on  all  installations  to  assure  proper  operation  and  to  prevent  debris  from  entering  the  venting 

system. 

 

E.

 Vertical runs must use a fire-stop as a lateral support at each ceiling level and at least one support at the base of the vertical run 

where required by the appliance manufacturer. For vertical runs exceeding 16 ft (4.88m), a support collar is required at 16 ft 

(4.88m) intervals. Support horizontal runs using loose fitting metal straps as hangers and similar supports at each elbow. 

 

 

F:

 

It  may  be  required  to  have  more  than  one  condensate  drain  on  a  single  vent  system

.  Therefore  it  is 

recommended  that 

vertical

  and 

horizontal

 

drain  tees

  with  3inch  p-traps  be  installed  on  long  vent  systems  in  order  to 

eliminate the system of condensate as quickly as possible.  

Note:

  

These Drain Tees & Traps must be accessible for 

future inspections. 

 

 

 

 

 

Содержание Z-Vent SVE III Series

Страница 1: ...and contract Pipe must be properly supported Proper joint assembly is essential for a safe installation Follow these instructions exactly as written Check severeness of joints upon completion of assem...

Страница 2: ...e more than 3 ft 91 m from any other building opening gas utility meter service regulator or the like 6 Exterior mounted venting systems should be enclosed below the roof line with a chase to limit co...

Страница 3: ...rds termination NOTE Some flue collars may require the use of high temperature silicone sealant to make a positive pressure gas tight seal IMAGES 1 2 3 CLEARANCE TO COMBUSTIBLES SIDE WALL VENTING INST...

Страница 4: ...I III or IV appliances or downwards for Category III or IV appliances not less than 1 4 6 4 mm every 12 inches 305 mm to prevent collection of condensate at any location in the assembly Fasteners must...

Страница 5: ...5 IMAGE 8 IMAGE 9 ILLUSTRATION 2...

Страница 6: ...installed Where the vent passes through the roof a flashing must be used to maintain the required clearances and to protect from the elements The framed opening must be large enough to provide the nec...

Страница 7: ...be used to support the system 1 Install the Guy Band below the Rain Cap using the 10 24 screw and nut provided 2 Attach stainless steel or galvanized cable with a minimum rated capacity of 500lbs to e...

Страница 8: ...last pipe length and attach top support to pipe Leave 6 150 mm of pipe protruding from flashing so that rain cap may be installed and to allow for any adjustment to line up base tee properly see image...

Страница 9: ...s are completed be sure to go over the entire system to make sure all joints are secure and sealed correctly The seams and joints must be checked for tightness prior to using the venting system A qual...

Страница 10: ...XPRESS WARRANTY HAS BEEN MADE OR WILL BE MADE ON BEHALF OF SELLER WITH RESPECT TO THE Z VENT OR THE INSTALLATION OR REPLACEMENT OF THE Z VENT SELLER SHALL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL INDI...

Отзывы: