Conducting a Forward Purge
Figure 228
1. Place the NJEX System in Standby mode by
pressing the Standby key on the N-300 controller.
2. Close valves V8 and V6
3. Open valve V4 until pressure reaches 50-60 psi (3.4-4
Bar) in the expansion tank, then close valve V4.
4. Scroll to the Meter Level display on the N-300
controller
5. Open valve V2 until:
a) Empty is indicated in the Meter Level display
And
b) Gas bubbling in the bulk odorant storage tank
becomes audible.
6. Close valve V17
7. Proceed to the Venting Pressure Gas procedure on