7.10 View Mode (VIEW)
Displays information of the positioner. The user can change the valve stroke displays in
percent (%) or number format.
ITEM
Description
YT-3400
Positioner model
VERSION /
2016MR 8
Main software version / loading date of software
You can toggle them, pushing <ENTER>
HART REV
HART protocol version
POL AddR
HART protocol channel address
You can change it, pushing <ENTER>
bIAS 25
BIAS value when valve position is at 25%
bIAS 75
BIAS value when valve position is at 75%
0Y 0d
Total used time duration. If a unit was used less than 1 minute, the
time will not accumulate.
FULL_OP
Time elapsed for valve to fully open
FULL_CL
Time elapsed for valve to fully close.
VM NOR /
VM REVS
Type of valve stroke on LCD.
VM NOR : View Mode Normal. 4mA -> 0%, 20mA -> 100% display
VM REVS : View Mode Revers. 4mA -> 100%, 20mA -> 0% display
You can change it, pushing <ENTER>
Erro
Error code(C, D) or warning code(B, F, G, H). Refer to 8.1 or 8.2
sections
⇨
<ENTER>
6 seconds
⇨
<DOWN>
6 times
⇨
<ENTER>
⇨
<UP>/<DOWN>
Confirm the
chages, then
<ESC>
2 times
⇨
<ENTER>
<DOWN>
⇨
<ENTER>
<ESC>
3 times