6.2 Troubleshooting a non-operating DPI-208 and DPI-480 Microinverter

6. Troubleshooting

There are two possible overall areas of trouble:

A) 

The Microinverter itself may be having problems.

B)

 The Microinverter itself is working fine but it is having trouble communicating with the ECU. The items 

below refer to Microinverter issues, not communication issues (addressed in the ECU manual).

A quick way to tell whether the issue is wih the Microinverter or a communication problem with the ECU:

1)

 Diagnosing the Microinverter: A red light – either blinking or solid on the Microinverter, or no light at all. 

No light, or a red light, means it is definitely a Microinverter problem.

2)

 Diagnosing from the ECU:

A)

 No-Data-Display: This is probably a communication issue, not a Microinverter problem.

B)

 Problems with erratic display: Data is displayed for some period and then no data is displayed. Most   

likely a communication issue.

C)

 0 watts, or 2 watts: Possibly a Microinverter problem.  

D)

 Erratic data display that is not coordinating with data displays from other units is most likely a Microin-

verter problem.

To troubleshoot a non-operating DPI-208 and DPI-480 Microinverter, 

Follow the steps below in order:

No need for maintenance.

Do not attempt to repair the DPI-208 and DPI-480 Microinverter. If troubleshooting 

methods fail, please return the microinverter to your distributor for replacement.

6.3 Maintenance

1)

 Verify the utility voltage and frequency are within ranges shown in the Technical Data section of this 

manual.

2)

 Check the connection to the utility grid. Verify utility power is present at the inverter in question by 

removing AC, then DC power. Never disconnect the DC wires while the microinverter is producing power. 

Re-connect the DC module connectors and watch for three short LED flashes.

3)

 Check the AC branch circuit interconnection between all the microinverters. Verify each inverter is 

energized by the utility grid as described in the previous step.

4)

 Make sure that any AC breaker are functioning properly and are closed.

5)

 Check the DC connections between the microinverter and the PV module.

6)

 Verify the PV module DC voltage is within the allowable range shown in the Technical Data of this 

manual.

7)

 If the problem persists, please call Yotta Energy Customer Support.

15

Содержание DPI-208

Страница 1: ...Installation User manual Ver 1 0 September 2022 DPI 208 DPI 480...

Страница 2: ...Microinverter to AC bus cable 11 4 4 6 Step 6 Install a AC bus protective end cap at the end of AC bus cable 11 4 4 7 Step 7 Connect DPI 208 and DPI 480 Microinverters to the PV Modules 12 4 4 8 Step...

Страница 3: ...arn ing notices in the technical documents and on the DPI 208 and DPI 480 Microinverter system and the solar array Be aware that the case of the DPI 208 or DPI 480 Microinverter is the heat sink and c...

Страница 4: ...technical for help Changes or modi cations not expressly approved by the party responsible for compliance may void the user s authority to operate the equipment Federal Communication Commission Inter...

Страница 5: ...killed person to enable him or her to perceive risks and to avoid hazards which electricity can create For the purpose of the safety informa tion of this manual a quali ed person is someone who is fam...

Страница 6: ...d DPI 480 Microinverter is used in utility interactive grid tied applications com prised of three key elements Yotta DPI 208 and DPI 480 Microinverter Yotta Energy Communication Unit ECU Yotta Energy...

Страница 7: ...ich one module underperforms compared with the other units the Yotta DPI 208 and DPI 480 Microinverter ensures top performance from the array by maximizing the performance of each module pair within t...

Страница 8: ...family bene ts from an entirely new architecture The components are encapsulated with silicone to reduce stress on the electronics facilitate thermal dissipation enhance waterproof properties and ensu...

Страница 9: ...tself as well as on the PV array Be aware that installation of this equipment includes the risk of electric shock Do not touch any live parts in the system including the PV array when the system has b...

Страница 10: ...tic system which initiates rapid shutdown upon the activation of a system disconnect or activation of another type of emergency system The initiator shall be listed and identi ed as a disconnecting me...

Страница 11: ...dule junction box or any other obstructions B Mount one Microinverter at each of these locations using hardware recommended by your module racking vendor When installing the Microinverter make sure th...

Страница 12: ...k Use the Bus Cable Unlock Tool of AC Bus to split the connectors NOTE AC connector interface should be as shown NOTE Cover any unusued con nectors with bus cable Y CONN caps to protect the connectors...

Страница 13: ...to these lights when connecting the DC cables 4 4 8 Step 8 Complete the DPI 208 and DPI 480 installation map Fill in the Yotta Registration Cards which provide system information and the Installation...

Страница 14: ...espective loca tion on the Yotta DPI 208 and DPI 480 Installation Map Yotta DPI 208 and DPI 480 Microinverter Energy Communication Unit Warranty 4 Yotta DPI 208 and DPI 480 System Installation A The l...

Страница 15: ...e Microinverters they will start to blink green every 10 sec onds 4 Install and setup the ECU according to the instructions in the ECU manual 5 The Yotta DPI 208 and DPI 480 Microinverters will start...

Страница 16: ...a Ground Fault Detector Interrupter GFDI error in the PV system Unless the GFDI error has been cleared the LED will remain red and the ECU will keep reporting the fault After the ground fault error is...

Страница 17: ...ther units is most likely a Microin verter problem To troubleshoot a non operating DPI 208 and DPI 480 Microinverter Follow the steps below in order No need for maintenance Do not attempt to repair th...

Страница 18: ...e rst AC connector in the branch circuit 3 Disconnect the PV module DC wire connectors from the microinverter 4 Remove the Microinverter from the PV array racking C Install a replacement Microinverter...

Страница 19: ...e and current speci cations of your PV module match with those of the Microinverter Please refer to the datasheet or user manual 2 You must match the DC operating voltage range of the PV module with t...

Страница 20: ...torage Temperature Range 40 F to 185 F 40 C to 85 C Dimensions W x H x D 14 9 5 1 8 359mm X 242mm X 46mm Weight 13 lbs 6kg DC Connector Type St ubli MC4 PV ADBP4 S2 ADSP4 S2 Cooling Natural Convection...

Страница 21: ...8 1 DPI 208 and DPI 480 Microinverter Datasheet Note 1 Utility Interconnection Voltage and Frequency Trip Limits and Trip Times 19...

Страница 22: ...9 Wiring Diagram 9 1 DPI 208 and DPI 480 Connected to Delta grids 20 ECU Energy Communication Unit JB Delta Grid Connections 3 Phase Cable no N or GND Black L1 Red L2 Blue L3...

Страница 23: ...ECU Energy Communication Unit JB WYE Grid Connections 3 Phase Cable no N or GND Black L1 Red L2 Blue L3 9 Wiring Diagram 9 2 DPI 208 and DPI 480 Connected to WYE grids 21...

Страница 24: ...10 DPI 208 and DPI 480 Accesories 10 1 Wiring Diagram 22...

Страница 25: ...10 DPI 208 and DPI 480 Accesories 10 2 Accesories Summary 23...

Страница 26: ...Yotta DPI 208 and DPI 480 Microinverter Energy Communication Unit Warranty Card Warranty Card...

Отзывы: