5. Maximum Continuous Discharge Capacity
1. Discharging capability of the air trap differs by working differential pressure, that is, difference between
inlet pressure and outlet pressure (back pressure). In selecting discharge capacity, consider outlet
pressure. If inlet pressure is 0.5 MPa and outlet pressure is 0.2 MPa, discharge capacity is of working
differential pressure of 0.3 MPa.
2.
The discharge capacity shown in the charts below is the maximum value. In designing a system, select
an air trap with a sufficient safety factor (two times the regular level). That is, for example, if a discharge
capacity of 500 kg/h is required, select a steam trap capable of discharging more than 1,000 kg/h
(maximum discharge).