Johnson Controls Unitary Products
ZF240 (20 Ton) Bottom Duct Imperial
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static 6.3 HP & Field Supplied Drive
High Static 6.3 HP & OEM Drive
5200
711 1.47 747 1.92 782 2.34 818 2.73 853 3.09 887 3.42 921 3.70 953 3.94 985 4.13 1014 4.26 1042 4.34 1068 4.35
5600
732 1.89 768 2.33 803 2.76 839 3.15 874 3.51 908 3.84 942 4.12 974 4.36 1005 4.54 1035 4.68 1063 4.75 1089 4.76
6000
754 2.35 790 2.79 826 3.21 862 3.61 897 3.97 931 4.29 965 4.58 997 4.81 1028 5.00 1058 5.14 1086 5.21 1112 5.22
6400
779 2.85 814 3.29 850 3.71 886 4.11 921 4.47 955 4.79 989 5.08 1021 5.31 1052 5.50 1082 5.64 1110 5.71 1136 5.72
6800
804 3.39 840 3.84 876 4.26 912 4.65 947 5.01 981 5.34 1015 5.62 1047 5.86 1078 6.05 1108 6.18 1136 6.26 1162 6.27
7200
832 3.98 868 4.43 903 4.85 939 5.24 974 5.60 1008 5.93 1042 6.21 1074 6.45 1105 6.64 1135 6.77 1163 6.85 1189 6.86
7600
860 4.62 896 5.06 932 5.49 967 5.88 1002 6.24 1037 6.56 1070 6.85 1103 7.09 1134 7.27 1164 7.41 1192 7.48
-
-
8000
890 5.30 926 5.74 962 6.17 997 6.56 1032 6.92 1067 7.24 1100 7.53 1133 7.77 1164 7.95 1194 8.09
-
-
-
-
8400
921 6.02 957 6.47 993 6.89 1028 7.28 1064 7.64 1098 7.97 1131 8.25 1164 8.49 1195 8.68
-
-
-
-
-
-
8800
954 6.79 989 7.24 1025 7.66 1061 8.05 1096 8.41 1130 8.74
-
-
-
-
-
-
-
-
-
-
-
-
9200
987 7.60 1023 8.05 1059 8.47 1094 8.86
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
9600
1021 8.45 1057 8.90
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10000
546 4.89 564 5.11
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive
ZF240 (20 Ton) Bottom Duct Metric
Air
FlowM3/
sec.
Available External Static Pressure - Pa
1
100
149
199
249
299
349
399
448
498
548
598
648
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
High Static 6.3 HP & Field Supplied Drive
High Static 6.3 HP & OEM Drive
2.45
711 1.10 747 1.43 782 1.75 818 2.04 853 2.30 887 2.55 921 2.76 953 2.94 985 3.08 1014 3.18 1042 3.24 1068 3.24
2.64
732 1.41 768 1.74 803 2.06 839 2.35 874 2.62 908 2.86 942 3.07 974 3.25 1005 3.39 1035 3.49 1063 3.54 1089 3.55
2.83
754 1.75 790 2.08 826 2.39 862 2.69 897 2.82 931 3.20 965 3.42 997 3.59 1028 3.72 1058 3.83 1086 3.89 1112 3.89
3.02
779 2.13 814 2.45 850 2.77 886 3.07 921 3.33 955 3.57 989 3.79 1021 3.96 1052 4.10 1082 4.21 1110 4.26 1136 4.27
3.21
804 2.53 840 2.86 876 3.18 912 3.47 947 3.74 981 3.98 1015 4.19 1047 4.37 1078 4.51 1108 4.61 1136 4.67 1162 4.68
3.40
832 2.97 868 3.30 903 3.62 939 3.91 974 4.18 1008 4.42 1042 4.63 1074 4.81 1105 4.95 1135 5.05 1163 5.11 1189 5.12
3.59
860 3.45 896 3.77 932 4.09 967 4.39 1002 4.65 1037 4.89 1070 5.11 1103 5.29 1134 5.42 1164 5.53 1192 5.58
-
-
3.78
890 3.95 926 4.28 962
4.6
997 4.89 1032 5.16 1067 5.40 1100 5.62 1133 5.79 1164 5.93 1194 6.03
-
-
-
-
3.96
921 4.49 957 4.82 993 5.14 1028 5.43 1064 5.70 1098 5.94 1131 6.15 1164 6.33 1195 6.47
-
-
-
-
-
-
4.15
954 5.06 989 5.40 1025 5.71 1061 6.00 1096 6.27 1130 6.52
-
-
-
-
-
-
-
-
-
-
-
-
4.34
987 5.67 1023 6.00 1059 6.32 1094 6.61
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.53
1021 6.30 1057 6.64
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.