Johnson Controls Unitary Products
ZF240 (20 Ton) Side Duct Imperial
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static 6.3 HP & Field Supplied Drive
High Static 6.3 HP & OEM Drive
5200
678 1.35 715 1.83 751 2.28 787 2.70 823 3.09 858 3.43 892 3.74 925 3.99 957 4.19 987 4.33 1015 4.41 1042 4.42
5600
697 1.74 733 2.22 770 2.67 806 3.09 842 3.48 876 3.82 911 4.13 944 4.38 975 4.58 1005 4.72 1034 4.80 1060 4.82
6000
717 2.17 754 2.65 790 3.10 826 3.52 862 3.90 897 4.25 931 4.55 964 4.81 996 5.01 1026 5.15 1054 5.23 1081 5.24
6400
740 2.64 776 3.11 812 3.57 848 3.99 884 4.37 919 4.72 953 5.02 986 5.28 1018 5.48 1048 5.62 1076 5.70 1103 5.71
6800
763 3.15 800 3.63 836 4.08 872 4.50 908 4.88 943 5.23 977 5.53 1010 5.79 1042 5.99 1072 6.13 1100 6.21 1127 6.22
7200
789 3.71 825 4.18 861 4.63 898 5.05 933 5.44 968 5.79 1002 6.09 1035 6.34 1067 6.55 1097 6.69 1126 6.77 1152 6.78
7600
815 4.31 852 4.79 888 5.24 924 5.66 960 6.04 995 6.39 1029 6.69 1062 6.95 1094 7.15 1124 7.29 1152 7.37 1179 7.38
8000
844 4.96 880 5.44 916 5.89 952 6.31 988 6.70 1023 7.04 1057 7.34 1090 7.60 1122 7.80 1152 7.94 1180 8.02 1207 8.03
8400
873 5.66 909 6.13 946 6.59 982 7.01 1018 7.39 1053 7.74 1087 8.04 1120 8.30 1151 8.50 1182 8.64
-
-
-
-
8800
904 6.40 940 6.88 977 7.33 1013 7.75 1048 8.14 1083 8.48 1117 8.79
-
-
-
-
-
-
-
-
-
-
9200
936 7.19 972 7.67 1009 8.12 1045 8.54 1080 8.93
-
-
-
-
-
-
-
-
-
-
-
-
-
-
9600
969 8.03 1005 8.50 1042 8.96
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10000
1003 8.91
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive
ZF240 (20 Ton) Side Duct Metric
Air
Flow
M
3
/sec.
Available External Static Pressure - Pa
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
100
149
199
249
299
349
399
448
498
548
598
648
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
High Static 6.3 HP & Field Supplied Drive
High Static 6.3 HP & OEM Drive
2.45
678
1.01
715
1.36
751
1.70
787
2.01
823
2.30
858
2.56
892
2.79
925
2.98
957
3.12
987
3.23 1015 3.29 1042 3.30
2.64
697
1.30
733
1.66
770
1.99
806
2.30
842
2.60
876
2.85
911
3.08
944
3.27
975
3.42 1005 3.52 1034 3.58 1060 3.59
2.83
717
1.62
754
1.98
790
2.31
826
2.62
862
2.91
897
3.17
931
3.39
964
3.59
996
3.74 1026 3.84 1054 3.90 1081 3.91
3.02
740
1.97
776
2.32
812
2.66
848
2.98
884
3.26
919
3.52
953
3.74
986
3.94 1018 4.09 1048 4.19 1076 4.25 1103 4.26
3.21
763
2.35
800
2.71
836
3.04
872
3.36
908
3.64
943
3.90
977
4.12 1010 4.32 1042 4.47 1072 4.57 1100 4.63 1127 4.64
3.40
789
2.77
825
3.12
861
3.45
898
3.77
933
4.06
968
4.32 1002 4.54 1035 4.73 1067 4.88 1097 4.99 1126 5.05 1152 5.06
3.59
815
3.21
852
3.57
888
3.91
924
4.22
960
4.50
995
4.77 1029 4.99 1062 5.18 1094 5.33 1124 5.44 1152 5.50 1179 5.50
3.78
844
3.70
880
4.06
916
4.39
952
4.71
988
5.00 1023 5.25 1057 5.47 1090 5.67 1122 8.82 1152 5.92 1180 5.98 1207 5.99
3.96
873
4.22
909
4.57
946
4.91
982
5.23 1018 5.51 1053 5.77 1087 6.00 1120 6.19 1151 6.34 1182 6.44 1210 6.50
-
-
4.15
904
4.77
940
5.13
977
5.47 1013 5.78 1048 6.07 1083 6.32 1117 6.55
-
-
-
-
-
-
-
-
-
-
4.34
936
5.36
972
5.70 1009 6.06 1045 6.37 1080 6.66
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.53
969
5.99 1005 6.34 1042 6.68
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.72
1003 6.64
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive