VSD DATA AND OPERATING HOURS/START COUNTER KEYS
LD19539
FIGURE 51 -
VSD DATA AND OPERATING HOURS/START COUNTER KEYS
VSD DATA
KEY
OPERATING
HOURS/START
COUNTER KEY
The VSD DATA key provides multiple displays of
VSD operating data, such as voltages and currents.
Press the VSD DATA, or ▲ or ▼ key to view multiple
messages, which are explained below.
VSD FREQUENCY
ACTUAL = ###.# HZ
COMMAND = ###.# HZ
VSD COMP = ### AMPS = ### % FLA
This key displays the calculated COMPRESSOR mo-
tor currents.
VSD CURRENT LIMIT LOCAL = ### %FLA
BAS = ###
REMOTE = ### %FLA
CURRENT LIMIT displays the current limit values as
set under the PROGRAM key, remotely by a BAS, and
REMOTE CURRENT LIMIT input. Inactive current
limits will display XX instead of a numeric value.
VSD DC BUS VOLTAGE = ### VDC
VSD
INTERNAL AMBIENT TEMP = ###.# °F
COOLING SYSTEM STATUS = ON OR OFF
VSD IGBT BASEPLATE TEMPS T1 = ### °F
T2
=
### °F
VSD
PRECHARGE SIGNAL = ON OR OFF
VSD
COMP MOTOR OVERLOAD = ### AMPS
This message (above) displays the setting of the VSD's
105% FLA potentiometer for the Compressors. The
settings are determined by the adjustment of the over-
load potentiometers on the VSD logic board, which are
factory set, and should not require changing unless the
circuit board is replaced.
Operating Hours/Start Counter Key
HOURS 1=###, 2=###
START 1=###, 2=###
Compressor operating HOURS and STARTS are dis-
played with a single key press. The maximum value
is 99,999, at which point both values roll over to zero.
Содержание YVWA
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 64: ...JOHNSON CONTROLS 64 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...JOHNSON CONTROLS 82 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 146: ...JOHNSON CONTROLS 146 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 152: ...JOHNSON CONTROLS 152 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 155: ...JOHNSON CONTROLS 155 NOTES...