SECTION 6 - OPERATION
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
6
MESSAGE
DESCRIPTION
YYYYYYY HPCO
Hardware-Initiated Fault -
The mechanical High Pressure Cutout (HPCO) protects the system
from experiencing dangerously high discharge pressure. A system will fault and shut down
immediately when the mechanical high pressure cutout contacts open. The fault will occur
immediately and not wait three seconds. The HPCO is wired in series with the VSD run signal
and will only be checked by the control board when the system is running.
TABLE 34 -
HPCO MECHANICAL CUTOUTS
HPCO
DESCRIPTION
OPEN
CLOSE
PSIG (MPa)
+ / -
PSIG (MPa)
+ / -
025-39956-001
337 (2.32)
8 (0.05)
230 (1.58)
10 (0.07)
025-39956-002
299 (2.06)
7 (0.05)
200 (1.37)
10 (0.07)
025-39956-003
341 (2.35)
7 (0.05)
200 (1.37)
10 (0.07)
025-39956-004
204 (1.40)
7 (0.05)
120 (0.82)
10 (0.07)
YYYYYYY will show FAULT to indicate a system is in a FAULT condition, and will restart when
the 120 second anti-recycle timer times out; or will show LOCKOUT, and the system will not
restart until the operator clears the fault using the keypad.
YYYYYYY LOW DIFF
OIL PRESSURE
This fault protects the compressor from low oil flow causing insufficient lubrication. A system
will fault and shut down with a ramped shutdown when its differential between oil and suction
pressure falls below the fault. The safety is ignored for the first 60 seconds of run time. If restart
transition has occurred, the timer is set according to
with a maximum limit
of 73 seconds. The timer calculation allows for 60 seconds of run time after the time it takes to
ramp the running compressor from its existing speed to shutdown speed.
TABLE 35 -
TIMER SETTINGS
CURRENT
FREQUENCY
INCREASE TIMER BY:
>100 Hz
60 sec. + (100 Hz - 5 Hz)/30.4 Hz/sec + 9.5 sec.
< or = 100 Hz
60 sec. + (Current freq - 5 Hz)/10 Hz/sec
NOTE:
9.5 sec = (100 Hz-5 Hz/10 Hz sec), the time it takes to ramp from 100 Hz to 5 Hz.
After the timer expires, the fault is linearly ramped from 0 psid (0 kPa) to the programmable
threshold (20-60 psid, default 25 psid (137-413 kPa, default 172 kPa) in 10 minutes. If the VSD
frequency is less than 50 Hz when the differential pressure falls below the limit, the three second
start-up bypass time will be increased to 30 seconds. Under these conditions, the slow speed
of the running compressor causes the oil differential to become very low, especially if the water
temperature and the suction pressure are high. The bypass make sure the compressor will not
trip on a nuisance low oil differential fault. This auto-restart safety will lock out on the third fault
in 90 minutes. YYYYYYY will show FAULT to indicate a system is in a FAULT condition, and will
restart when the 120 second anti-recycle timer times out; or will show LOCKOUT, and the system
will not restart until the operator clears the fault using the keypad.
YYYYYYY LOW
DISCHARGE
SUPERHEAT
This fault protects against excessive liquid refrigerant carryover from the evaporator, in cases
which may be a result of overcharge of refrigerant or another refrigerant inventory problem. It
also protects the compressor from liquid refrigerant flooding back from the economizer feed line,
in cases where the economizer valve fails to close. This safety is ignored for the first 10 minutes
of system run time. If the discharge superheat falls below 5.0°F (2.8°C) for ten minutes, the
system will shutdown. This fault causes a lockout on the third fault in 90 minutes. YYYYYYY will
show FAULT to indicate a FAULT condition, and will restart when the 120 second anti-recycle
timer times out; or will show LOCKOUT, and the system will not restart until the operator clears
the fault using the keypad.
TABLE 33 -
SYSTEM SAFETIES FAULTS (CONT'D)
Содержание YVWA
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 64: ...JOHNSON CONTROLS 64 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...JOHNSON CONTROLS 82 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 146: ...JOHNSON CONTROLS 146 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 152: ...JOHNSON CONTROLS 152 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 155: ...JOHNSON CONTROLS 155 NOTES...