Mainboard and Fan2 communication failure
16P
Driver hardware overcurrent
101
Compressor driving failure
102
Compressor overcurrent
103
Reserved
104
Sampling failure of compressor current
105
Heat sink/IPM overheating alarm
106
Pre-charge failure
107
DC bus over voltage
108
DC bus under voltage
109
AC input under voltage
110
AC input overcurrent
111
Driver check out failure
112
AC input hardware overcurrent
113
Driver temperature sensor fault
114
FOCx drive failure
115
FOCx/APFCx overcurrent
116
Running Status
Press “FUNCTION” and “CONFIRM” keys for 5 seconds to enter Running Status viewing screen. The digital and
analog inputs and outputs are displayed in sequence in hour display area (Area 1) by pressing “UP” and “DOWN”
keys.
The modules can be switched over by pressing “TIMER” key.
Description of each running status parameters as shown in Table 21
TABLE 13
– DESCRIPTION OF RUNNING STATUS
(
012~018
)
Running status No.
Description
A1
AI1 Refrigerant temperature inlet accumulator
A2
AI2 Saturate temperature of suction pressure
A3
AI3 Discharge temperature
A4
AI4 Ambient temperature
A5
AI5 System leaving water temperature
A6
AI6 System return water temperature
A7
AI7 Unit leaving water temperature
A8
AI8 Coil temperature
17
Open steps of expansion valve
21
Rotary speed of BLDC fan 1
22
Rotary speed of BLDC fan 2
23
Compressor frequency loading rate
24
Software version of Microboard
26
Software version of wire controller
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz
Содержание YVAG012
Страница 53: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz ...
Страница 54: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz ...
Страница 55: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz ...