Parameters related to defrost
Display
Description
Level
VS
Unit
Max.
Min.
Value
d01
Execution of defrost 0= no (function not available)
1= yes.
U
7 (R/W)
-
1
0
1
d02
Time or temperature defrost.
0= time (function not available).
1= temperature / pressure
U
8 (R/W)
-
1
0
1
d03
Defrost start temperature / pressure
U
19 (R/W)
°C
bar
d04
-40/
11
-3
6.2
d04
Defrost end temperature / pressure
U
21 (R/W)
°C
bar
80/
12
d03
20
14.4
d05
Minimum time for defrost start
U
37 (R/W)
sec.
150
10
10
d06
Minimum defrost duration
U
38 (R/W)
sec.
150
0
0
d07
Maximum defrost duration
U
39 (R/W)
Min.
15
1
6
d08
Time between two defrost cycles
U
40 (R/W)
Min.
150
10
30
d11
Activation heaters in defrost
0= no.
1= yes.
U
9 (R/W)
-
0
1
1
d12
Compressor OFF before defrost
F
43 (R/W)
Min.
3
0
1
d13
Compressor OFF after defrost
F
44 (R/W)
Min.
3
0
1
d16
Time of forced vent after defrost
(only if F13=2).
F
47 (R/W)
sec.
360
0
60
DEFROST START
END DEFROST
(d06) MAXIMUM
DURATION DEFROST
TIMING START
(d05) MINIMUM TIME
DEFROST START
(d04) DEFROST END
TEMPERATURE
(d03) DEFROST START
TEMPERATURE
t