42
(a) YLCA/YLHA PLUS 5 to 15 /03=1; YLCA/YLHA PLUS 5 to 15 LAK 03/=2; YLCA/YLHA PLUS 20 to 27 03/=2.
(b) YLCA/YLHA PLUS 5 to 15 /04=2; YLCA/YLHA PLUS 5 to 15 LAK 04/=3. YLCA/YLHA PLUS 20 to 27 04/=3.
Parameters related to the probes
Display
Description
Level
VS
Unit
Max.
Min.
Value
/01
NTC B1 probe (water intake); 0=absent (function not available).
1=present
F
1 (R/W)
-
1
0
1
/02
NTC B2 probe (water outlet). 0=absent (function not available).
1=present
F
2 (R/W)
-
1
0
1
/03
NTC B3 probe . 1=condensation probe. 2=outdoor probe.
F
14 (R/W)
-
1
0
(a)
/04
Probe type B4. 0=absent. 1=ON/OFF. 2=outdoor NTC probe. 3=ratio-
metric 5Vdc.
F
15 (R/W)
-
3
0
(b)
/09
Minimum input voltage
F
18 (R/W) 0.01 Vdc
/10
0
50
/10
Maximum input voltage
F
19 (R/W) 0.01 Vdc
500
/09
450
/11
Minimum pressure
F
1 (R/W)
bar
/12
0
0
/12
Maximum pressure
F
2 (R/W)
bar
99.9
/11
45
/13
Calibration probe B1
F
3 (R/W)
°C
12
-12
0
/14
Calibration probe B2
F
4 (R/W)
°C
12
-12
0
/15
Calibration probe B3
F
5 (R/W)
°C
12
-12
0
/16
Calibration probe B4
F
6 (R/W)
bar
12
-12
0
/21
Digital filter
U
20 (R/W)
-
15
1
4
/22
Input limitation
U
21 (R/W)
-
15
1
8
/23
Measuring unit 0 = C; 1 = 1F
U
5 (R/W)
-
1
0
0
b00
Probe viewed on display
U
24 (R/W)
-
7
0
0
b01
Value read by probe B1
D
70 (R)
°C
-
-
-
b02
Value read by probe B2
D
71 (R)
°C
-
-
-
b03
Value read by probe B3
D
72 (R)
°C
-
-
-
b04
Value read by probe B4
D
73 (R)
°C/bar
-
-
-
Parameters related to the probes
Display
Description
Level
VS
Unit
Max
Min
Value
c01
Minimum operating time
U
25 (R/W)
Sec.
999
0
60
c02
Minimum OFF time
U
26 (R/W)
Sec.
999
0
60
c03
Time between start-ups of the same compressor
U
27 (R/W)
Sec.
999
0
300
c06
Start-up timed
U
30 (R/W)
Sec.
999
0
10
c07
Compressor start-up delay with regard to the pump
U
31 (R/W)
Sec.
150
0
20
c08
Pump OFF delay with regard to the compressor
U
32 (R/W)
Min.
150
0
1
c10
Operating hour counter compressor
D
90 (R)
Hours
800
0
-
c14
Operating hour counter for compressor maintenance
U
34 (R/W)
Hours
100
0
0
c15
Operating hour counter for pump
D
94 (R/W)
Hours
800
0
-
c17
Minimum time between pump start-ups
U
35 (R/W)
Min.
150
0
5
c18
Minimum operating time for pump
U
36 (R/W)
Min.
15
0
1