background image

JOHNSON CONTROLS

31

SECTION 6 - MAINTENANCE

FORM 160.76-O1 

ISSUE DATE: 6/15/2015

6

Acid cleaning should only be performed 

by an expert. Please consult your local 

water treatment representative for as-

sistance in removing scale buildup and 

preventative maintenance programs to 

eliminate future problems. COMMER-

CIAL ACID CLEANING

In many major cities, commercial organizations now 

offer a specialized service of acid cleaning evaporators 

and condensers. If acid cleaning is required, YORK 

recommends the use of this type of organization. The 

Dow Industries Service Division of the Dow Chemical 

Company, Tulsa, Oklahoma, with branches in principal 

cities is one of the most reliable of these companies.

Testing For Evaporator And Condenser Tube 

Leaks

Evaporator and condenser tube leaks in R-134a sys-

tems may result in refrigerant leaking into the water 

circuit, or water leaking into the shell depending on the 

pressure levels. If refrigerant is leaking into the water, 

it can be detected at the liquid head vents after a period 

of shutdown. If water is leaking into the refrigerant, 

system capacity and efficiency will drop off sharply. If 

a tube is leaking and water has entered the system, the 

evaporator and condenser should be valved off from 

the rest of the water circuit and drained immediately to 

prevent severe rusting and corrosion. The refrigerant 

system should then be drained and purged with dry ni-

trogen to prevent severe rusting and corrosion. If a tube 

leak is indicated, the exact location of the leak may be 

determined as follows:

1.  Remove the heads and listen at each section of 

tubes for a hissing sound that would indicate gas 

leakage. This will assist in locating the section of 

tubes to be further investigated. If the probable 

location of the leaky tubes has been determined, 

treat that section in the following manner (if the 

location is not definite, all the tubes will require 

investigations).

2.  Wash off both tube heads and the ends of all tubes 

with water.

Do not use carbon tetrachloride for this 

purpose since its fumes give the same 

flame discoloration that the refrigerant 

does. 

3.  With nitrogen or dry air, blow out the tubes to 

clear them of traces of refrigerant laden moisture 

from the circulation water. As soon as the tubes 

are clear, a cork should be driven into each end 

of the tube. Pressurize the dry system with 50 to 

100 PSIG (345 to 690 kPa) of nitrogen. Repeat 

this with all of the other tubes in the suspected 

section or, if necessary, with all the tubes in the 

evaporator or condenser. Allow the evaporator or 

condenser to remain corked up to 12 to 24 hours 

before proceeding. Depending upon the amount 

of leakage, the corks may blow from the end of a 

tube, indicating the location of the leakage. If not, 

if will be necessary to make a very thorough test 

with the leak detector.

4.  After the tubes have been corked for 12 to 24 

hours, it is recommended that two men working 

at both ends of the evaporator carefully test each 

tube – one man removing corks at one end and 

the other at the opposite end to remove corks and 

handle the leak detector. Start with the top row of 

tubes in the section being investigated. Remove 

the corks at the ends of one tube simultaneously 

and insert the exploring tube for 5 seconds – this 

should be long enough to draw into the detec-

tor any refrigerant gas that might have leaked 

through the tube walls. A fan placed at the end of 

the evaporator opposite the detector will assure 

that any leakage will travel through the tube to 

the detector.

5. 

Mark any leaking tubes for later identification.

6.  If any of the tube sheet joints are leaking, the leak 

should be indicated by the detector. If a tube sheet 

leak is suspected, its exact location may be found 

by using a soap solution. A continuous buildup of 

bubbles around a tube indicates a tube sheet leak.

Содержание YK Series

Страница 1: ...WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER AND VARIABLE SPEED DRIVE CENTRIFUGAL LIQUID CHILLERS OPERATIONS AND MAINTENANCE New Release Form 160 76 O1 615 LD15222...

Страница 2: ...his document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in ques...

Страница 3: ...Chillers Style H Q3 Q7 with Low Voltage VSD 160 75 PW7 Renewal Parts Unit 160 76 RP1 Renewal Parts OptiView Control Center 160 54 RP1 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls...

Страница 4: ...6 15 2015 NOMENCLATURE YK 6A 6Q Q7 EM H MOTOR CODE POWER SUPPLY for 60 Hz 5 for 50 Hz COMPRESSOR CODE CONDENSER CODE EVAPORATOR CODE MODEL STYLE Design Level Refer to YK Engineering Guide for Form 16...

Страница 5: ...13 Stopping The System 13 Prolonged Shutdown 13 SECTION 3 SYSTEM COMPONENTS DESCRIPTION 15 General 15 Compressor 15 Capacity Control 15 Compressor Lubrication System 15 Oil Pump 15 Oil Heater 19 Moto...

Страница 6: ...10 Oil Return System 21 FIGURE 11 Charging Oil Reservoir With Oil 22 FIGURE 12 Evacuation Of Chiller 25 FIGURE 13 Saturation Curve 27 FIGURE 14 Diagram Megging Motor Windings 28 FIGURE 15 Motor Start...

Страница 7: ...in effect provides the performance of many different compressors to match various load conditions from full load with vanes wide open to minimum load with vanes completely closed SECTION 1 DESCRIPTIO...

Страница 8: ...owers ext jci com 717 771 7535 YK Mod G Refrigerant Flow Thru Cross Section Diagram Falling Film Evaporator LEGEND High Pressure Vapor High Pressure Liquid Refrigerant Low Pressure Liquid Refrigerant...

Страница 9: ...turn to the RUN position If the unit was previously started press the STOP RESET side of the COMPRESSOR switch and then press the START side of the switch to start the chill er When the start switch i...

Страница 10: ...hutdowns Refer to Display Messages in manual Optiview Control Center Operation and Maintenance Form 160 54 O1 Figure 5 CHILLER STARTING SEQUENCE AND SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 0 10 13 45 5...

Страница 11: ...he YORK chiller is designed to use less power by tak ing advantage of lower than design temperatures that are naturally produced by cooling towers throughout the operating year Exact control of conden...

Страница 12: ...ndenser saturation temperature based upon condenser pressure sensed by the condenser transducer on the SYSTEM Screen 6 Check the compressor discharge temperature on the SYSTEM Screen During normal ope...

Страница 13: ...he OptiView panel or rapid stop with the COM PRESSOR STOP RESET switch The compressor will stop automatically The oil pump will contin ue to run for coastdown period The oil pump will then stop automa...

Страница 14: ...JOHNSON CONTROLS 14 FORM 160 76 O1 ISSUE DATE 6 15 2015 SECTION 2 SYSTEM OPERATING PROCEDURES THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 15: ...supplied with forced lubrication as follows 1 Compressor Drive Shaft Low Speed a Shaft seal b Front and rear journal bearings one on each side of driving gear c Low speed thrust bearing forward and r...

Страница 16: ...6 15 2015 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FRONT VIEW Figure 7 SYSTEM COMPONENTS FRONT VIEW VARIABLE SPEED DRIVE EVAPORATOR COMPRESSOR SUCTION RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP...

Страница 17: ...7 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FORM 160 76 O1 ISSUE DATE 6 15 2015 3 3 LD15223 Figure 8 SYSTEM COMPONENTS REAR VIEW DISCHARGE LINE COMPRESSOR OIL PUMP HOUSING LIQUID LINE REAR VIEW MOTOR OI...

Страница 18: ...HT GLASSES OIL COOLER OIL TEMP CONTROL REFRIG THRUST COLLAR BEARING PRV INLET VALVES BEARING PINION GEAR SHAFT IMPELLER H S SHAFT SEAL LOW SPEED THRUST COVER LOW SPEED GEAR LOW SPEED GEAR REAR BEARING...

Страница 19: ...ogy to optimize efficiency minimize refrigerant charge and maintain reliable control A specifically designed spray distributor provides uniform distribution of re frigerant over the entire length to y...

Страница 20: ...Hot gas bypass is optional and is used to eliminate compressor surge during light load or high head op eration The OptiView control panel will automati cally modulate the hot gas valve open and closed...

Страница 21: ...m the evaporator through the dehy drator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following procedure 1 Isolate the dehydrator at the stop valves 2 Remove the de...

Страница 22: ...harge connection to the oil charg ing valve A located on the remote oil reservoir cover plate Refer to Figure 11 on Page 22 Do not tighten the connection at the charging valve until after the air is f...

Страница 23: ...ice problem Remove obstruction Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature Evaporator tubes dirty or re...

Страница 24: ...blocked oil supply inlet Check oil inlet for blockage 8 SYMPTOM OIL PRESSURE GRADUALLY DECREASES Noted by Observation of Daily Log Sheets When oil pump VSD frequency increases to 55 hz to maintain ta...

Страница 25: ...to be found by the soap test To test with R 134a proceed as follows 1 With no pressure in the system charge R 134a gas into the system through the charging valve to a pressure of 2 PSIG 14 kPa 2 Build...

Страница 26: ...es and shell are heated evenly 5 Close the system charging valve and the stop valve between the vacuum indicator and the vac uum pump Then disconnect the vacuum pump leaving the vacuum indicator in pl...

Страница 27: ...rior to evacuation then the saturation tempera ture recordings should follow a curve similar to the typ ical saturation curve shown as Figure 13 on Page 27 The temperature of the water in the test tub...

Страница 28: ...nt charge should always be checked and trimmed when the system is shut down The refrigerant charge level must be checked after the pressure and temperature have equalized between the condenser and eva...

Страница 29: ...e motor should not be run The motor should be heated to 250 F in an effort to remove moisture and obtain an acceptable reading at room ambient This can be done either by baking in a forced hot air ove...

Страница 30: ...ribute to erratic performance Condenser In a condenser trouble due to fouled tubes is usually indicated by a steady rise in head pressure over a pe riod of time accompanied by a steady rise in condens...

Страница 31: ...ection in the following manner if the location is not definite all the tubes will require investigations 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachloride...

Страница 32: ...it is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the presence of aluminum particles Aluminum gas seal rings can c...

Страница 33: ...common motors MOTOR RE LUBRICATION INSTRUCTION All motor manufacturers have slightly different re quirements for the exact amount of grease to be added and the exact interval for re greasing The sugge...

Страница 34: ...o see old grease coming out from the relief port Operating Temperature Normal operating temperature for grease lubricated bearings on York chillers is 40 65 degrees centigrade or 100 150 degrees Fahre...

Страница 35: ...evalu ated similiar to evaporator tubes when the heating circuit is a treated closed loop Fouling could be detected as ability to meet heat load requirements decreases OIL RETURN SYSTEM 1 Change the...

Страница 36: ...f applicable X 2 Perform oil analysis on compressor lube oil 1 X Perform refrigeration analysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Year...

Страница 37: ...Fahrenheit to Celsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 3 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons...

Страница 38: ...Freedom Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2015 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 76 O1 615 Issue Dat...

Отзывы: