ENGLISH
18
Figure 37: Recommended distance between trunking on
the wall and trunking on the heat pump is 300mm.
7.3. POSITION AND CONNECT OUTDOOR
SENSORS
!
NOTE! The power cable may only be connected to
the terminal block in tended for this purpose. No other
terminal blocks may be used!
Figure 38: Incoming cable to heat pump with circuit breaker.
!
NOTE! Supplied with the jumpers shown in the figure.
1.
Route the power cable through the opening in the top panel of
the heat pump to the terminal blocks.
2.
Connect the power cable to the terminal block.
!
NOTE! The outdoor sensor is connected with extra
low protection voltage. Follow the specific installation
instructions for the outdoor sensor!
Figure 40: Connecting the outdoor sensor.
l
Position the outdoor sensor on the north or north west side of
the house.
l
To measure the outdoor temperature as accurately as possible,
the sensor must be positioned 2/3 of the way up the facade on
houses up to three storeys high. For higher buildings, the sensor
should be positioned between the second and third storeys. Its
location must not be completely protected from the wind but not
in a direct draft. The outdoor sensor should not be placed on
reflective panel walls.
l
The sensor must be positioned at least 1 m from openings in the
walls that emit hot air.
l
If the sensor cable is connected through a pipe, the pipe must be
sealed so that the sensor is not affected by outgoing air.
The outdoor sensor is connected by a two core cable. For a cross
section of 0.75 mm2 a maximum cable length of 50 m applies.
For greater lengths a cross section of 1.5 mm2 is used, up to a
maximum of 120 m.
Then connect the sensor to the heat pump control system in
accordance with the instructions below.
Figure 41: Connecting the outdoor sensor.
1.
Route the outdoor sensor connection cable through the cable
bushing in the top panel to the terminal block.
2.
Connect the sensor to the terminal blocks according to the
connection diagram.
!
NOTE! The power cable may only be connected to
the terminal block intended for this purpose. No other
terminal blocks may be used!
Figure 39: Incoming cable to heat pump.
1.
Route the power cable through the opening in the top panel of
the heat pump to the terminal blocks.
2.
Connect the power cable to the terminal block.
Incoming 230v heat pump
Incoming 230v external auxiliary heater
7.1. CONNECT POWER SUPPLY, 400v 3N
7.2. CONNECT POWER SUPPLY, 230v 1N SP
H
2/3 x
H
Recommended location
Unsuitable location